Bus interface 12, Di1 12, Inp2 12 – West Control Solutions KS 45 User Manual
Page 12: Out1, out2 12, Out3 12, Inp1 12
3 Connecting input di1
Digital input, configurable as a switch or a push-button.
a
contact input
terminals: 7,8
b
optocoupler input (optional)
terminals: 7,8
4 Connecting outputs OUT1 / OUT2 (optional)
Relay outputs max. 250V/2A NO contacts with a common terminal.
•
OUT1
terminals: 17, 18
•
OUT2
terminals: 17, 14
5 Connecting output OUT3
Universal output
h
logic (0..20mA / 0..10V)
terminals: 11,12
i
current (0...20mA)
terminals: 11,12
j
voltage (0...10V)
terminals: 12,13
k
transmitter power supply
terminals: 11,12
6 Connecting the bus interface (optional exept d)
RS 485 interface with MODBUS RTU protocol
* see interface description MODBUS RTU: (9499-040-72011)
7 Connecting input INP2 (optional exept d)
Input for the second variable INP2.
a
thermocouple
terminals: 5,6
b
resistance thermometer (Pt100/ Pt1000/ KTY/ ...), 3-wire connection
terminals: 2,5,6
c
potentiometer
terminals: 2,5,6
d
current (0/4...20mA)
terminals: 2,6
e
voltage (-2,5...115/-25...1150/-25...90/ -500...500mV)
terminals; 5,6
8 Connection of input INP1 for the version with optional opto-coupler outputs
Input for the measured variable (measurement value).
a
resistance thermometer (Pt100/ Pt1000/ KTY/ ...), 3-wire connection
terminals: 1, 2, 3
c
potentiometer
terminals: 1, 2, 3
d
current (0/4...20mA)
terminals: 2, 3
e
voltage (-2,5...115/-25...1150/-25...90/ -500...500mV)
terminals: 1, 2
f
voltage (0/2...10V / -10...10V / -5...5V)
terminals: 2, 4
g
thermocouple
terminals: 1, 3
9 Connecting INP2 -HC (optional)
Input for heating current
•
Current 0/4...20mA DC and 0 … 50 mA AC
terminals: 5,6
0 Connecting opto-coupler outputs OUT1 / OUT2 (optional)
Opto-coupler outputs with shared positive control voltage.
•
OUT1
terminals: (11), 12, 13
•
OUT2
terminals: (11), 12, 14
! Connecting relay output OUT3 (optional)
Relay output max. 250V/2A as nomally open contact.
•
OUT3
terminals: 17, 18
Electrical connections
Terminal connections
12
KS 45