Technical data – KROHNE OPTIBAR PC 5060 C EN User Manual
Page 65
TECHNICAL DATA
7
65
OPTIBAR PC 5060 C
www.krohne.com
04/2014 - 4003437201 - MA OPTIBAR PC 5060 C R01 en
Inputs and outputs
Output signal
Output signal
Output signal
Output signal
Output signal
4...20 mA / HART
®
version 7.3
3.8...20.5 mA (factory setting acc. to. NAMUR recommendation)
Signal resolution
0.3 µA
Error signal of current
output (adjustable)
High alarm ≥21 mA
Low alarm ≤3.6 mA, last valid measurement
Max. output current
21.5 mA
Starting current
≤10 mA for 5 ms after switching on, then ≤3.6 mA
Damping
0...999 seconds, adjustable
Approvals and certificates
CE
The device fulfils the statutory requirements of the EC directives. The manufacturer
certifies that these requirements have been met by applying the CE marking.
Electromagnetic
compatibility (EMC)
EMC conformity for EN 61326-1 (05/2006)
NAMUR
NE 21 - Electromagnetic compatibility of equipment
NE 43 - Signal level for the failure information of digital transmitters
NE 53 - Compatibility of field devices and display/adjustment components
NE 107 - Self-monitoring and diagnosis of field devices
Classification according to
Pressure Equipment
Directive (PED 97/23/EC)
For gases of fluid group 1 and liquids of fluid group 1, the requirements are fulfilled
according to article 3, paragraph 3 (sound engineering practice).
.book Page 65 Friday, May 2, 2014 12:49 PM