48
OPTIBAR PC 5060 C
www.krohne.com
04/2014 - 4003437201 - MA OPTIBAR PC 5060 C R01 en
5.6 Saving the device settings
We recommended noting the parameters and archiving them afterwards. They are thus available
for multiple use or service purposes. If the pressure transmitter is equipped with a display and
adjustment module, the most important data can be read out of the sensor into the display and
adjustment module. The data remain there permanently even if the sensor power supply fails. If
it is necessary to exchange the signal converter, the display and adjustment module is inserted
into the replacement device and the data are written into the signal converter under the menu
item "Copy device data".
5.7 Diagnosis memory
The device has several internal memories which are available for diagnosis purposes. The data
remain even with voltage interruption.
Measured value memory
Measured value memory
Measured value memory
Measured value memory
Up to 60,000 measured values can be stored in a ring memory. Each entry contains a time stamp
as well as the respective measured value. Storable values are for example:
• Process pressure
• Level
• Percent value
• Linear percent
• Scaled values
• Meas. cell temp.
• Electronic temperature
With the default factory settings, the measured value memory is active and stores distance,
measurement reliability and electronics temperature every minute. The requested values and
recording conditions are set via a PC with PACTware
TM
/DTM or the control system with EDD.
.book Page 48 Friday, May 2, 2014 12:49 PM