5.3 Quick setup
To quickly and easily adapt the device to the application, select the menu item "Quick setup".
This parameter adjustment essentially involves the selection of the application, position
correction and adjustment of the span.
In this chapter, not all settings are displayed graphically but all settings are described.
1 Measurement loop name
Measurement loop name
Measurement loop name
Measurement loop name
Assign a suitable measurement loop name
2 Adjustment units
Adjustment units
Adjustment units
Adjustment units
Determine the adjustment and temperature units of the device.
3 Application
Application
Application
Application
The selection includes process pressure and level.
Adjustment process pressure
1 Sensor mounting correction
Sensor mounting correction
Sensor mounting correction
Sensor mounting correction
In this menu item you compensate the influence of the installation position of the device (offset) on the
measured value.
2 Zero
Zero
Zero
Zero
In this menu item you determine the zero point of your measurement (LRV)
This value corresponds to the output signal of 4 mA.
3 Span
Span
Span
Span
This value corresponds 100%, or rather an output signal of 20 mA (URV)
If the zero point is actually 0, this value corresponds to the measuring span.