Start-up, 5 reset – KROHNE OPTIBAR PC 5060 C EN User Manual
Page 47
START-UP
5
47
OPTIBAR PC 5060 C
www.krohne.com
04/2014 - 4003437201 - MA OPTIBAR PC 5060 C R01 en
5.5 Reset
The reset function resets specific user entries. There are two reset functions available:
Delivery status
Delivery status
Delivery status
Delivery status
Restore the default values at the time of delivery, including the order-specific settings. A false
signal suppression, user programmable linearization curve as well as the measured value
memory will be deleted.
Basic settings
Basic settings
Basic settings
Basic settings
Reset the set data, including special parameters to the default values of the manufacturer. A
false signal suppression, user programmable linearization curve as well as the measured value
memory will be deleted.
The following menu items are affected during a reset
Menu item
Parameter
Default
Measurement loop name
Sensor
Application
No reset
Unit
Adjustment units
mbar (cell ≤ 400 mbar)
bar (cell ≥ 1 bar)
Temperature unit
C°
Sensor mounting correction
0.00 bar
Adjustment
Zero / Min.-adjustment
0.00 bar - 0.00%
Span / Max.-adjustment
+URL in bar - 100%
Damping
Integration time
0.0 seconds
Current output
Current output mode
Output characteristic 4...20 mA
Failure mode ≤ 3.6 mA
Current output variable
Linear percent - Level
Current output, adjustment
0...100% = 4...20 mA
Current output min./max.
Min. 3.8 mA
Max. 20.5 mA
Lock adjustment
Unlock
Language
English
Displayed value 1
Current output in %
Displayed value 2
Meas. cell temp. in °C
Backlight
Off
Simulation
Process pressure
PIN
0000
Scaling
Scaling variable
Volume in L
Scaling format
0% = 0 L / 100% = 0 L
HART
®
mode
Address 0
.book Page 47 Friday, May 2, 2014 12:49 PM