TECHNICAL DATA

7

59

OPTIBAR PC 5060 C

www.krohne.com

04/2014 - 4003437201 - MA OPTIBAR PC 5060 C R01 en

7.2 Technical data

INFORMATION!

The following data is provided for general applications. If you require data that is more
relevant to your specific application, please contact us or your local sales office.

Additional information (certificates, special tools, software,...) and complete product
documentation can be downloaded free of charge from the website (Download Center).

Measuring system

Measuring principle

Capacitive ceramic measuring cell

Application range

Process pressure measurement

Level of liquids

Measuring range

25 mbar...100 bar / 0.73...1450.38 psi

Display and user interface

Display and user interface

Display and user interface

Display and user interface

Display on signal

converter

Dot-matrix display 45x27 mm / 1.77x1.06", illuminated

Display turnable in 90° steps

Digit size 13x7 mm / 0.51x0.27"

Ambient temperatures below -20°C / -4°F may affect the readability of the display

Display function

Display of measured value or derived measured value such as filling height

Warning and diagnostic information

All parameters are accessible via the operating menu

Operating and display

languages

German, English, French, Spanish, Portuguese, Italian, Dutch, Russian, Turkish, Polish and

Czech

Operation

Local operation via 4 push buttons on the display and adjustment module

Remote operation

PACTware

TM

, incl. Device Type Manager (DTM)

HART

®

Hand Held Communicator from Emerson Process

AMS

®

from Emerson Process

PDM

®

from Siemens

Integrated clock

Date format

Day / Month / Year

Time format

12 hours / 24 hours

Time zone

CET (Factory setting)

Rate deviation

Maximum 10.5 minutes / year

Measuring accuracy

Process pressure

Process pressure

Process pressure

Process pressure

Reference conditions

acc. to DIN 61298-1

Ambient temperature (constant): +15...+25°C / +59...+77°F

Relative humidity (constant): 45...75%

Ambient pressure (constant): 860...1060 mbar / 12.5...15.4 psi

Measuring accuracy according to IEC 61298-2 (terminal based)

Curve characteristic: linear

Vertical mounting position, measuring diaphragm pointing down

Effect of mounting position < 0.2 mbar/20 Pa (0.003 psig)

Deviation at current output due to strong, high-frequency electromagnetic fields within
the scope of EN 61326