Technical data, 2 technical data – KROHNE OPTIFLEX 1100C EN User Manual
Page 61
TECHNICAL DATA
8
61
OPTIFLEX 1100 C
www.krohne.com
01/2012 - 4001721801 - HB OPTIFLEX 1100 R01 en
8.2 Technical data
Converter
INFORMATION!
•
The following data is provided for general applications. If you require data that is more
relevant to your specific application, please contact us or your local representative.
•
Complete product documentation can be downloaded free of charge from the website
(Download Center).
Measuring system
Application
Level and volume measurement of liquids, pastes, powders and granulates
Measuring principle
TDR (time domain reflectometry)
Construction
Measuring probe attached directly to a signal converter
Operating conditions
Ambient temperature
-40…+80°C / -40…+176°F
Integrated LCD display: -20...+60°C / -5...+140°F; if the ambient temperature is not
in these limits, the display switches off
Storage temperature
-50…+85°C / -60…+185°F
Protection category
IP 66/67
Materials
Housing
Polyester-coated aluminium
Cable entry
M20 × 1.5 (plastic cable gland included) or ½ NPT (without cable gland)
Electrical connections
Power supply (terminals)
14…30 VDC
Current output load
R
L
[Ω] ≤ ((U
ext
-14 V)/22 mA). For more data, refer to
Minimum power supply voltage
on page 63.
Cable entry capacity (terminal)
0.5…1.5 mm²
Input and output
Measured variable
Time between the emitted and received signal
Output signal
4…20 mA or 3.8…20.5 mA
Resolution
±
1 µA
Error signal options
High: 22 mA; Low: 3.6 mA
Hold (frozen value)
Display and user interface
User interface options
LCD display (128 × 64 pixels in 8-step greyscale with 4-button keypad)
Languages
9 languages are available: English, German, French, Italian, Spanish, Portuguese,
Japanese, Chinese (Mandarin) and Russian