Operation – KROHNE OPTIFLEX 1100C EN User Manual
Page 55

OPERATION
6
55
OPTIFLEX 1100 C
www.krohne.com
01/2012 - 4001721801 - HB OPTIFLEX 1100 R01 en
The display
reading does not
change and the
current output
value is incorrect.
2
ERR 200
Reference
pulse lost
Reference amplitude
is less than reference
threshold. This fault
could occur because
the device hardware is
defective.
Contact your supplier to check
that the electronics are still
functioning correctly.
1
ERR 201
Sensor
voltage failure
The device's hardware
is defective.
Contact the supplier.
The display
reading does not
change and the
current output
value is incorrect.
4
ERR 202
Level lost
error
The device cannot find
the product surface.
Measure the level of the contents
in the tank using another method
of measurement. If the tank is
empty (the level is below the end
of the probe), then fill the tank
until product level is in the
measurement range. If the tank is
full (the level is in the blocking
distance), then remove the
contents from the tank until the
level is back in the measuring
range. If the product was lost and
the tank is neither full nor empty,
wait for the device to find the level
again.
The device cannot find
the level return signal
Refer to MEAS. AMP. (Measured
Pulse Amplitude, menu item
2.5.6) and then adjust MEAS.
THRESH. (measurement
threshold, menu item 2.5.7).
The measurement
and the current
output value stops
at the "full" value.
4
ERR 204
Overfill error
The tank is full. The
level signal is lost in
the full area. The
measurement stops at
the blocking distance
value.
Danger of overflow! Remove the
contents from the tank until it is
at a safe level.
The measurement
stops at the last
measured value
and the current
output value is
incorrect.
3
ERR 205
Measurement
old
This error occurs if
the power supply is
not sufficient to
operate the device
correctly for
approximately 30
seconds. After 1
minute the error
message
"Measurement old" is
recorded.
Make sure that the power supply
has a min./max. value of
14...30 VDC when current output
is at 22 mA.
3
ERR 206
No sensor
detected
This error occurs if
there is a problem
with the power supply.
Contact the supplier.
1
Defective wiring.
1
ERR 207
Sensor
memory
failure
The device's hardware
is defective.
Contact the supplier.
1
ERR 208
Oscillator
failure
The device's hardware
is defective.
Contact the supplier.
Problem
Status
marker
shown
Error
code
recorded
Error
Message
Cause
Corrective action