6
OPERATION
50
OPTIFLEX 1100 C
www.krohne.com
01/2012 - 4001721801 - HB OPTIFLEX 1100 R01 en
How to prepare a strapping table.
• Enter the supervisor menu.
• Press 6 × [
], [>>>>] and 2 × [
] to go to 2.7.2 LENGTH UNIT.
• Press [
] and [
] to find the length unit that you will use in the table.
• Press [^
^
^
^] to go to the sub-menu level.
• Press [
] to go to 2.7.3 CONV UNIT (conversion unit)
• Press [
] and [
] to find the conversion unit that you will use in the table.
• Press [^
^
^
^] to go to the sub-menu level and then U and > to go to the menu item 2.8.1 INPUT
TAB
• Press [>>>>] to make the strapping table. Enter the number of data pairs in the table.
• Enter the length value and press [^
^
^
^].
• Enter the conversion value and press [^
^
^
^].
• Repeat the last 2 steps to complete the table.
The device creates a table of up to 30 pairs of data (level - volume or level - mass). The reference
point for the table is the bottom of the tank (as given in menu item 2.3.1 TANK HEIGHT).
The device will give more accurate volume readings if you give more conversion data in these
areas:
• Surfaces with curves.
• Sudden changes in the cross section.
Refer also to the illustration that follows:
Figure 6-3: A plot of points for a volume or mass table
1 with reference points
2 model with plotted points