OPERATION

6

49

OPTIFLEX 1100 C

www.krohne.com

01/2012 - 4001721801 - HB OPTIFLEX 1100 R01 en

6.4.5 Level measurement

The device current output agrees with the level measurement when the output is set to
"Level". Menu items related to level measurement are:

• Output Function (2.4.1 OUTPUT)
• Tank Height (2.3.1 TANK HEIGHT)
• Blocking Distance (2.3.4 BLOC. DIST.)

Use the tank bottom as the reference point for the 4 and 20 mA current output settings. The 4
and 20 mA current output settings are the minimum and maximum points of the measurement
scale.

For more data about the menu items, refer to

Function description

on page 38.

6.4.6 How to configure the device to measure volume or mass

The device can be configured to measure volume or mass. You can set up a strapping table in the
conversion table (2.8.0 CONV. TAB) sub-menu.

Figure 6-2: Level measurement

1 Tank Height (2.3.1 TANK HEIGHT)
2 Blocking Distance (2.3.4 BLOC. DIST.)
3 Maximum effective measuring range
4 20 mA Setting (2.4.4 SCALE 20mA)
5 4 mA Setting (2.4.3 SCALE 4mA)
6 Non-measurement zone