2.4.1

OUTPUT FUNC.

The output function. Select an

output function to scale the

current values in relation to a

given point (usually the device

process connection or the tank

bottom). The output current

value is shown on a bar graph

in normal mode if the

measurement name is the

same as the output function.

Conversion parameters are

shown if there is volume or

mass data in 2.8.1 INPUT

TABLE.

Distance, Level,

Conversion, Ullage

Conversion

Level

2.4.2

RANGE I

This parameter sets the range

of the current output with

(3.8...20.5 mA) or without

(4...20 mA) over-run values. It

also tells the device what to do

if an error occurs. For example,

the device will change to an

error value of 22 mA if you set

RANGE I to 4-20/22E

4-20/22E

4-20/22E

4-20/22E. If you set

RANGE I to 4-20

4-20

4-20

4-20 and the device

senses a measurement error,

the value will stop at the last

correct measurement.

4-20, 4-20/22E,

4-20/3.6E, 3.8-

20.5/22E, 3.8-

20.5/3.6E

4-20/3.6E

2.4.3

SCALE 4mA

This gives a measurement

value to 4 mA.

min.-max:

2

For level

For level

For level

For level

Single cable

probes:

200 mm / 8¨;

Coaxial probe:

0 mm / 0¨

2.4.4

SCALE 20mA

This gives a measurement

value to 20 mA.

min.-max:

2

For level

For level

For level

For level

Single cable

probes: Probe

length -

450 mm / 18¨;

Coaxial probe:

Probe length -

250 mm / 10¨

2.4.5

ERROR DELAY

The time after which the

current output changes to an

error value. The error value

shows that there is a

measurement error.

MN=minutes and S=seconds.

0 S, 10 S, 20 S, 30 S,

1 MN, 2 MN,

5 MN,15 MN

10 S

2.5.0

APPLICATION

Use this sub-menu to configure

the device when there are

difficult process conditions.

Only approved personnel can

change these parameters.

2.5.1

TRACING VEL.

Tracing velocity. This value

must agree with the maximum

rate of change of the level of

the liquid or solid contents in

the tank.

min-max:

0.1…1000 m/min

10.0 m/min

2.5.2

AUTO Er CALC

Automatic dielectric constant

r

) calculation. The device

automatically calculates the ε

r

value of the liquid or solid

contents in the tank.

YES, NO

NO

Menu
No.

Function

Function description

Selection list

Default