beautypg.com

KROHNE Summit 8800 Vol 1 User Manual

Page 68

background image

68

www.krohne.com

08/2013 - MA SUMMIT 8800 Vol1 R02 en

SUMMIT 8800

FIELD DEVICE CONNECTION

06

Figure 69 Start/stop signals loop

6 .2 RS 232/RS485 Communications Connections

All I/O boards - Digital, Digital 2, Switch and Analog have an RS232/RS485 connection for serial

communications, with e.g., smart meters or similar devices. These connections are not galvani-

cally isolated from the internal supplies of the SUMMIT 8800; it is, therefore, recommended that

external barrier devices are used in conjunction with these connections.

RS232 connection:

Phoenix Contact PSM-ME-RS232/RS232-P

RS485 connections:

Phoenix Contact PSM-ME-RS485/RS485-P
Phoenix Contact PSM-ME-RS232/RS485-P

The communication boards have 3 separate galvanically isolated RS232/RS485 connections for

such as serial communication to printers, supervisory systems or gas chromatographs.

If RS485 communication is to be used on any of the boards, string termination must be consid-

ered.

To connect the termination resistor chain both links associated with the RS485 connection

should be set to the ON position.

NOTE: The figure below shows link references for the digital and analog I/O board only. Refer to

Contents for section on link references for the communication board.