beautypg.com

6 .1 .2 digital transmitter input connections – KROHNE Summit 8800 Vol 1 User Manual

Page 61

background image

61

www.krohne.com

08/2013 - MA SUMMIT 8800 Vol1 R02 en

SUMMIT 8800

FIELD DEVICE CONNECTION

06

Figure 55 HART multidrop

6 .1 .2 Digital Transmitter Input Connections

These inputs are generally used for connection to pulse-counting meters such as Rotary or

Turbine meters, frequency measuring transmitters such as Density or Relative Density trans-

mitters or simple switch inputs. In all cases the required connections is typically as shown in the

figure below.

It is intended that the Input be connected to a +24V pulse input with Link LK8 in the off position,

this allows an input current of 10mA to flow. If the pulse source is operated from different volt-

age sources then LK8 should be switched to the ON position and an external resistor of value

that will allow 10mA to flow should be fitted in series with the D I/P 1+ Terminal.

Typical voltages and resistor values are given in the next table.

Voltage

Resistor

15V

1k5

12V

1k1

5V

510

Table 21 Digital transmitter reference voltage and resistance

For terminal pin designations refer to the connections of the I/O board used.

Reference should be made to the meter or transmitter manual for correct installation and con-

nectivity guidance.