beautypg.com

KROHNE Summit 8800 Vol 1 User Manual

Page 19

background image

19

www.krohne.com

08/2013 - MA SUMMIT 8800 Vol1 R02 en

SUMMIT 8800

DESCRIPTION

03

3 .1 .4 Rear Panel Layout

Figure 2 Rear view of SUMMIT 8800

3 .1 .5 Alarms & LED’s

Figure 3 LED indicators

Power ON

This indicates that the SUMMIT 8800 is receiving an input power and is operating.

Accountable Alarm

These are alarms that need direct action because they could have effect on the result of the

calculations.

Accountable alarms are red and can be defined via the Configurator under stream n.

These are user defined values set within variable parameters such as temperature, pressure,

density. Within each run, the user can configure the minimum and maximum value for the

variable operating range. This alarm typically indicates that the full operating range has been

reached.

Non-accountable Alarm

These are user defined values set within variable parameters such as temperature, pressure,

density. Within each run, the user can configure the high and low value for the variable operat-

ing range which typically is always less than the maximum and minimum values entered. This

alarm typically indicates that the desirable operating range is being exceeded.