5 .9 ethernet boards, 5 .8 .2 .4 digital input / outputs settings – KROHNE Summit 8800 Vol 1 User Manual
Page 53
53
www.krohne.com
08/2013 - MA SUMMIT 8800 Vol1 R02 en
SUMMIT 8800
HARDWARE DETAILS
05
Link Function
Factory
setting
3
RS485 termination network connection OFF
2
RS485 termination network connection OFF
Figure 46 Switch I/O board RS485 termination link settings
Table 14 Serial settings on switch I/O board
5 .8 .2 .4 Digital Input / Outputs Settings
Position of digital I/O links shown in the centre of the switch I/O board
Link
Function
Factory
setting
Input
Output
SW1-A
Digital I/O 1 input
Digital I/O 1 output Input
SW1-B
Digital I/O 2 input
Digital I/O 2 output Input
SW1-C
Digital I/O 3 input
Digital I/O 3 output Input
SW1-D
Digital I/O 4 input
Digital I/O 4 output Input
SW1-E
Digital I/O 5 input
Digital I/O 5 output Input
Figure 47 Switch I/O board digital input / output link settings
Table 15 Switch I/O board digital settings
5 .9 Ethernet boards
Two types of Ethernet boards are available: Dual and single Ethernet.
The dual ethernet network board is a qualified personnel exchangeable plug in card, up to a
maximum of 6 can be inserted in any of the user plug in slots in the SUMMIT 8800 chassis. It
provides system communication functions as follows:
• 1 galvanically isolated Serial Communication Port using either RS232 with full hand shaking
or RS485 standards providing connection to a serial printer.
• 2 galvanically isolated Serial Communication Ports using either RS232 with software hand-
shaking or RS485 standards providing connections to data logging or supervisory devices.
• 2 of Communication Port using Ethernet 10/100 providing connection to other Network en-
abled equipment.
The single Ethernet board is identical except that it only has one Ethernet port.
Comms Board
Serial connection Ethernet ports Advance Capabilities
Single Ethernet
3
1
No
Dual Ethernet
3
2
Yes*
Table 16 Communication board configuration