beautypg.com

5 .6 digital i/o board 2 – KROHNE Summit 8800 Vol 1 User Manual

Page 45

background image

45

www.krohne.com

08/2013 - MA SUMMIT 8800 Vol1 R02 en

SUMMIT 8800

HARDWARE DETAILS

05

5 .6 Digital I/O Board 2

The digital I/O board 2 can only be exchanged by qualified personnel. Up to a maximum of 6

cards can be inserted in any of the 6 plug in slots in the SUMMIT 8800 chassis. A board can pro-

vide input and output functions as detailed:

• 3 pulse counting/frequency measuring inputs (for use with turbine meters, rotary meters,

density or relative density transducers).

• 1 Digital status inputs for use with switch or contact inputs.

• 2 Smart transmitter (HART) loops. Each loop can provide connections for up to 3 transmitters

each with four variables such as pressure, temperature or differential pressure transmitters.

• 6 digital transistor switched outputs for use in telemetry systems or for alarm indication.

• 4 analog 4-20 mA outputs for use in telemetry or control systems.

• 1 Serial communication port using either (RS232 or half duplex RS485), providing connection

to gas meters, gas chromatographs or other equipment that transfers data via serial commu-

nication.

NOTE: Only configure pulse output 1 for Prover corrected bus.

An individual stream (or run) can be monitored by one digital I/O board as it provides all the nec-

essary inputs and outputs. Note that individual inputs and outputs can be configured separately

and are not limited to a specific measurement run.

5 .6 .1 Digital /O Board 2 Terminal Connections

Figure 35 Digital I/O board 2 rear terminal pin allocation