OPERATION

4

79

GFC 300

www.krohne.com

07/2012 - 4001866001 - AD GFC 300 FF R01 en

Value

R

Value of ROUT_OUT

-

SHED_OPT

SHED_OPT

SHED_OPT

SHED_OPT

Shed Options

Shed Options

Shed Options

Shed Options

R/W

Defines action to be taken on remote control device timeout.

Uninitialized

Setting:

Uninitialized

NormalShed_NormalReturn: Actual mode changes to next
lowest priority non-remote mode permitted, but returns to
target remote mode after communications are re-
established

NormalShed_NoReturn: Target mode changes to next
lowest priority non-remote mode permitted

ShedToAuto_NormalReturn: Actual mode changes to "Auto",
but returns to target remote mode after communications are
re-established

ShedToAuto_NoReturn: Target mode changes to "Auto"

ShedToManual_NormalReturn: Actual mode changes to
"Manual", but returns to target remote mode after
communications are re-established

NormalShed_NoReturn: Target mode changes to next
lowest priority non-remote mode permitted

ShedToRetainedTarget_NormalReturn: Shed to previous
target mode and return target remote mode after
communications are re-established

ShedToRetainedTarget_NoReturn: Target mode changes to
target retained mode

SP

SP

SP

SP

Setpoint

Setpoint

Setpoint

Setpoint

R/W

Setpoint

0

Status

Status of SP

Value

Value of SP

SP_HI_LIM

SP_HI_LIM

SP_HI_LIM

SP_HI_LIM

Setpoint High Limit

Setpoint High Limit

Setpoint High Limit

Setpoint High Limit

R/W

The setpoint high limit is the highest setpoint operator entry

that can be used for the block.

100

SP_LO_LIM

SP_LO_LIM

SP_LO_LIM

SP_LO_LIM

Setpoint Low Limit

Setpoint Low Limit

Setpoint Low Limit

Setpoint Low Limit

R/W

The setpoint low limit is the highest setpoint operator entry

that can be used for the block.

0

SP_RATE_DN

SP_RATE_DN

SP_RATE_DN

SP_RATE_DN

Setpoint Rate

Setpoint Rate

Setpoint Rate

Setpoint Rate

Down

Down

Down

Down

R/W

Ramp rate at which downward setpoint changes are acted on

in "Auto" mode, in PV units per second. If the ramp rate is set

to zero or the block is in a mode other than "Auto", then the

setpoint will be used immediately.

+INF

Setting:

0.0...+INF

SP_RATE_UP

SP_RATE_UP

SP_RATE_UP

SP_RATE_UP

Setpoint Rate Up

Setpoint Rate Up

Setpoint Rate Up

Setpoint Rate Up

R/W

Ramp rate at which upward setpoint changes are acted on in

"Auto" mode, in PV units per second. If the ramp rate is set to

zero or the block is in a mode other than "Auto", then the

setpoint will be used immediately.

+INF

Setting:

0.0...+INF

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value