OPERATION

4

27

GFC 300

www.krohne.com

07/2012 - 4001866001 - AD GFC 300 FF R01 en

SIMULATE

SIMULATE

SIMULATE

SIMULATE

Simulate

Simulate

Simulate

Simulate

Mix

Allows the transducer analogue input or output to the block to

be manually supplied when "Simulate" is enabled. When

simulation is disabled, the simulate value and status track the

actual value and status.

-

Simulate Status

R/W

Used for the transducer status when simulation is enabled.

0

Simulate Value

R/W

Used for the transducer value when simulation is enabled.

0.0

Setting:

-3.39 E38 … +3.39 E38, - INF, + INF

Transducer Status

R

Status of value supplied by transducer.

0

Transducer Value

R

Current value supplied by transducer.

0.0

Simulate

En/Disable

R/W

The parameter "SW_Simulated" in RB Block must be enabled. Disabled

Setting:

Uninitialized / Disabled / Active

STATUS_OPTS

STATUS_OPTS

STATUS_OPTS

STATUS_OPTS

Status Option

Status Option

Status Option

Status Option

R/W

Options which the user may select in the block processing of

status.

Uninitialized

Setting:

Propagate Fault Forward / Uncertain if limited / BAD if

limited / Uncertain if Man.

UPDATE_EVT

UPDATE_EVT

UPDATE_EVT

UPDATE_EVT

Update Event

Update Event

Update Event

Update Event

This alert is generated by any change to the static data.

-

Unacknowledged

RW

A discrete enumeration which is set to "Unacknowledged"

when an alarm occurs, and set to "Acknowledged" by a write

from a human interface device or other entity which can

acknowledge that the alarm/event has been noticed.

Uninitialized

Setting:

Uninitialized / Acknowledged / Unacknowledged

Update State

R

A discrete enumeration which gives an indication of whether

the alert has been reported.

Uninitialized

Setting:

Uninitialized / Reported / Not Reported

Time Stamp

R

The time when evaluation of the block was started and a

change in alarm/event state was detected that is unreported.

The time stamp value will be maintained constant until alert

confirmation has been received - even if another change of

state occurs. Time stamp records the time when parameter

was updated.

Uninitialized

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

Static Revision

R

The static revision of the block whose static parameter was

changed and is being reported. It is possible for the present

value of static revision to be greater than this because static

can be changed at any time.

0

Relative Index

R

The OD index of the static parameter whose change caused

this alert, minus the FB starting index. If the update event was

caused by a write to multiple parameters at the same time,

then this attribute will be zero.

0

XD_SCALE

XD_SCALE

XD_SCALE

XD_SCALE

Transducer Scale

Transducer Scale

Transducer Scale

Transducer Scale

R/W

The high and low scale values, engineering units code and

number of digits to the right of the decimal point used with the

value obtained from the transducer for a specified channel.

Note:

Note:

Note:

Note:

W = Writeable only by setting "OOS" in MODE_BLK

-

EU_100

EU at 100%

R/W

The engineering unit value which represents the upper end of

range of the associated block parameter.

100

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value