ELECTRICAL CONNECTIONS

3

7

GFC 300

www.krohne.com

07/2012 - 4001866001 - AD GFC 300 FF R01 en

3.4 Topology of FF networks

An example of mixed topology of FF networks is shown in the following example.

Connection is best made via short branch cables and T connectors. This connection type makes it
possible to connect and disconnect the devices without interrupting the bus or the
communication.

1

HSE network

2

H1 bus

3

Intrisically safe, explosive area

B1+B2

Bridge = coupling element for H1 bus
and HSE network

D1-D3

Device = field devices, own power
supply, for non potentially explosive
areas

D4-D6

Intrinsically safe devices, external
power supply, for potentially explosive
areas

I.S.

Intrinsically safe barrier

JB

Junction box for field devices

PS

Power supply
Switch = connection of multiple HSE
sub networks

T

Terminator