TB3_DIAG

TB 3

R

Reason for bits set at BLK_ERR and other diagnosis.

Current diagnosis

Startup Device / RB: MODE_BLK.ACTUAL is OOS / Memory

failure / no GDC Communication / Startup GDC, data invalid /

Startup Sensor, data valid / Data Base doesn't match to FF

Software / MODE_BLK.PERMITTED doesn't include Auto /

MODE_BLK.TARGET is set OOS / GDC bold F message / GDC F

message / write from GDC to RB/TB doesn't work / Sensor

serial number / Sensor calibration date / GDC unit not

convertible to TB.prim_val / prim_val is outside range /

action: write from GDC to RB/TB / GDC Communication few

loss / no unit of GDC / GDC unit can't be converted to

TB.prim_range / a GDC value was not received / a GDC short

status is fatal or warn2 / PRIMARY_VALUE_1.status is

Uncertain / unknown reason / Ok

AI1/2/3/4/5/6_DIAG

AI1/2/3/4/5/6

Diagnosis

R

Reason for OUT.status not Good, bits at BLK_ERR and other

diagnosis.

Current diagnosis

Setting:

Startup Device / RB : MODE_BLK.ACTUAL is OOS / Memory

failure / no schedule / period of execution / period of

execution to large / MODE_BLK.PERMITTED doesn't include

Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is

set MAN / MODE_BLK.ACTUAL is MAN , Startup to Auto /

CHANNEL is uninitialized / UNIT of CHANNEL selected

TB.prim_val not convertible to XD UNIT / XD_SCALE :

difference between EU_100 and EU_0 is to less / OUT_SCALE :

difference between EU_100 and EU_0 is to less / L_TYPE is

uninitialized / L_TYPE is direct , XD_SCALE is not equal

OUT_SCALE / IO_OPTS no unit conversion , XD UNIT doesn’t

match to UNIT of TB.prim_val / SIMULATE_STATUS is not

Good , Simulation is active / SIMULATE_STATUS limitted ,

STATUS_OPTS is set , Simulation active / Simulation is active /

Transducer Block MODE_BLK.ACTUAL is OOS / CHANNEL

selected TB.prim_val.status is Bad / TB.prim_val.status is

limitted , STATUS_OPTS is set / CHANNEL selected

TB.prim_val.status is Uncertain / OUT.value exceeds

OUT_SCALE / unknown reason / Ok

PID_DIAG

PID Diagnosis

R

Reason for OUT.status not Good, bits at BLK_ERR and other

diagnosis.

Current diagnosis

Setting:

Startup Device / RB: MODE_BLK.ACTUAL is OOS / Memory

failure / no schedule / period of execution / period of

execution to large / MODE_BLK.PERMITTED doesn't include

Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is

set MAN / MODE_BLK.ACTUAL is MAN, Startup to Auto /

BYPASS is uninitialized / SHED_OPT is uninitialized /

PV_SCALE : EU_100 <= EU_0 / OUT_SCALE: EU_100 <= EU_0 /

TRK_SCALE: EU_100 <= EU_0 / FF_SCALE: EU_100 <= EU_0 /

unknown reason / Ok

IT1/2_DIAG

IT1/2 Diagnosis

R

Reason for OUT.status not Good, bits at BLK_ERR and other

diagnosis.

Current diagnosis

Setting:

Startup Device / RB: MODE_BLK.ACTUAL is OOS / Memory

failure / no schedule / period of execution / period of

execution to large / MODE_BLK.PERMITTED doesn't include

Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is

set MAN / MODE_BLK.ACTUAL is MAN, Startup to Auto /

INTEG_TYPE is uninitialized / IN_1 and IN_2 are not

connected / TIME_UNIT1 and TIME_UNIT2 are uninitialized /

CLOCK_PER <= period of execution / TIME_UNIT and

TIME_UNIT2 is uninitialized / IN_1.status is Bad / IN_2.status

is Bad / IN_1.value is NaN or INF / IN_2.value is NaN or INF /

PCT_INCL < UNCERT_LIM / PCT_INCL < GOOD_LIM /

PULSE_VAL1 and PULSE_VAL2 are 0 / TOTAL_SP is 0: cyclic

reset / unknown reason / Ok

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value