Operation – KROHNE GFC 300 FOUNDATION FIELDBUS User Manual
Page 18
4
OPERATION
18
GFC 300
www.krohne.com
07/2012 - 4001866001 - AD GFC 300 FF R01 en
TB3_DIAG
TB 3
R
Reason for bits set at BLK_ERR and other diagnosis.
Current diagnosis
Startup Device / RB: MODE_BLK.ACTUAL is OOS / Memory
failure / no GDC Communication / Startup GDC, data invalid /
Startup Sensor, data valid / Data Base doesn't match to FF
Software / MODE_BLK.PERMITTED doesn't include Auto /
MODE_BLK.TARGET is set OOS / GDC bold F message / GDC F
message / write from GDC to RB/TB doesn't work / Sensor
serial number / Sensor calibration date / GDC unit not
convertible to TB.prim_val / prim_val is outside range /
action: write from GDC to RB/TB / GDC Communication few
loss / no unit of GDC / GDC unit can't be converted to
TB.prim_range / a GDC value was not received / a GDC short
status is fatal or warn2 / PRIMARY_VALUE_1.status is
Uncertain / unknown reason / Ok
AI1/2/3/4/5/6_DIAG
AI1/2/3/4/5/6
Diagnosis
R
Reason for OUT.status not Good, bits at BLK_ERR and other
diagnosis.
Current diagnosis
Setting:
Startup Device / RB : MODE_BLK.ACTUAL is OOS / Memory
failure / no schedule / period of execution / period of
execution to large / MODE_BLK.PERMITTED doesn't include
Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is
set MAN / MODE_BLK.ACTUAL is MAN , Startup to Auto /
CHANNEL is uninitialized / UNIT of CHANNEL selected
TB.prim_val not convertible to XD UNIT / XD_SCALE :
difference between EU_100 and EU_0 is to less / OUT_SCALE :
difference between EU_100 and EU_0 is to less / L_TYPE is
uninitialized / L_TYPE is direct , XD_SCALE is not equal
OUT_SCALE / IO_OPTS no unit conversion , XD UNIT doesn’t
match to UNIT of TB.prim_val / SIMULATE_STATUS is not
Good , Simulation is active / SIMULATE_STATUS limitted ,
STATUS_OPTS is set , Simulation active / Simulation is active /
Transducer Block MODE_BLK.ACTUAL is OOS / CHANNEL
selected TB.prim_val.status is Bad / TB.prim_val.status is
limitted , STATUS_OPTS is set / CHANNEL selected
TB.prim_val.status is Uncertain / OUT.value exceeds
OUT_SCALE / unknown reason / Ok
PID_DIAG
PID Diagnosis
R
Reason for OUT.status not Good, bits at BLK_ERR and other
diagnosis.
Current diagnosis
Setting:
Startup Device / RB: MODE_BLK.ACTUAL is OOS / Memory
failure / no schedule / period of execution / period of
execution to large / MODE_BLK.PERMITTED doesn't include
Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is
set MAN / MODE_BLK.ACTUAL is MAN, Startup to Auto /
BYPASS is uninitialized / SHED_OPT is uninitialized /
PV_SCALE : EU_100 <= EU_0 / OUT_SCALE: EU_100 <= EU_0 /
TRK_SCALE: EU_100 <= EU_0 / FF_SCALE: EU_100 <= EU_0 /
unknown reason / Ok
IT1/2_DIAG
IT1/2 Diagnosis
R
Reason for OUT.status not Good, bits at BLK_ERR and other
diagnosis.
Current diagnosis
Setting:
Startup Device / RB: MODE_BLK.ACTUAL is OOS / Memory
failure / no schedule / period of execution / period of
execution to large / MODE_BLK.PERMITTED doesn't include
Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is
set MAN / MODE_BLK.ACTUAL is MAN, Startup to Auto /
INTEG_TYPE is uninitialized / IN_1 and IN_2 are not
connected / TIME_UNIT1 and TIME_UNIT2 are uninitialized /
CLOCK_PER <= period of execution / TIME_UNIT and
TIME_UNIT2 is uninitialized / IN_1.status is Bad / IN_2.status
is Bad / IN_1.value is NaN or INF / IN_2.value is NaN or INF /
PCT_INCL < UNCERT_LIM / PCT_INCL < GOOD_LIM /
PULSE_VAL1 and PULSE_VAL2 are 0 / TOTAL_SP is 0: cyclic
reset / unknown reason / Ok
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value