OPERATION

38

GFC 300

www.krohne.com

07/2012 - 4001866001 - AD GFC 300 FF R01 en

VoS_Tolerance

VoS tolerance

R/W

Difference between measured and calculated Vos that will not

generate an VoS alarm (Fct. C1.8.4).

5.0

Settings:

0.0...25.00

Time_Constant_S

time constant

R/W

Time constant to account for in VoS monitor function (Fct.

C1.8.5).

1800.0

Settings:

60.0…3600.0

SENSOR_CAL_

SENSOR_CAL_

SENSOR_CAL_

SENSOR_CAL_

DATE

DATE

DATE

DATE

Sensor Calibration

Date

R

The date of the last sensor calibration.

-

SENSOR_

SENSOR_

SENSOR_

SENSOR_

DIAMETER

DIAMETER

DIAMETER

DIAMETER

meter size

R/W

Pipe diameter of the sensor (Fct. C1.1).

100

Settings:

25.0…1000.0

SENSOR_SN

SENSOR_SN

SENSOR_SN

SENSOR_SN

Sensor Serial

Number

R

The sensor serial number.

-

SENSOR_TYPE

SENSOR_TYPE

SENSOR_TYPE

SENSOR_TYPE

Sensor Type

R

The type of sensor.

Ultrasonic

TRANSDUCER_

TRANSDUCER_

TRANSDUCER_

TRANSDUCER_

DIRECTORY

DIRECTORY

DIRECTORY

DIRECTORY

Transducer

Directory Entry

A directory that specifies the number and starting indices of

the data collections in the transducer block.

0

TRANSDUCER_

TRANSDUCER_

TRANSDUCER_

TRANSDUCER_

TYPE

TYPE

TYPE

TYPE

Transducer Type

R

Identifies the transducer that follows.

Other

V_NO_SENSOR

V_NO_SENSOR

V_NO_SENSOR

V_NO_SENSOR

V no. sensor

R

(Fct. C1.6.6)

-

XD_ERROR

XD_ERROR

XD_ERROR

XD_ERROR

Transducer Error

One of the transducer error codes defined in the FF

Transducer Specifications in section "4.7 Block Alarm

Subcodes".

Uninitialized

Settings:

16: Unspecified error

17: General error

18: Calibration error

19: Configuration error

20: Electronics Failure

21: Mechanical Failure

22: I/O Failure

23: Data Integrity Error

24: Software Error

25: Algorithm Error

ZERO_

ZERO_

ZERO_

ZERO_

CALIBRATION

CALIBRATION

CALIBRATION

CALIBRATION

zero calibration

R/W

(Fct. C1.2)

Calib_Action

action

R/W

(Fct. C1.2.1)

no action

Settings:

no action / default / automatic

Calib_Status

status

R

not active / calibration running / calibration OK / calibration

NOK

calibration OK

Calib_Time

runtime

R

Remaining time needed for calibration

0

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value