Operation – KROHNE GFC 300 FOUNDATION FIELDBUS User Manual
Page 19
OPERATION
4
19
GFC 300
www.krohne.com
07/2012 - 4001866001 - AD GFC 300 FF R01 en
AR_DIAG
AR Diagnosis
R
Reason for OUT.status not Good, bits at BLK_ERR and other
diagnosis.
Current diagnosis
Startup Device / RB: MODE_BLK.ACTUAL is OOS / Memory
failure / no schedule / period of execution / period of
execution to large / MODE_BLK.PERMITTED doesn't include
Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is
set MAN / MODE_BLK.ACTUAL is MAN, Startup to Auto /
ARITH_TYPE is uninitialized / RANGE_HI < RANGE_LO /
COMP_LIM_HI < COMP_LIM_LO / OUT_LIM_HI < OUT_LIM_LO
/ IN_x.status is Bad / unknown reason / Ok
DIAGNOSIS_DEV
DIAGNOSIS_DEV
DIAGNOSIS_DEV
DIAGNOSIS_DEV
Diagnosis Device
Diagnosis Device
Diagnosis Device
Diagnosis Device
R
Display of maximum 8 (error) messages.
Current diagnosis
Setting:
No message
F:
F:
F:
F: error in device / IO 1 / parameter / IO 2 / configuration /
display / current in-/output A / current in-/output B / current
in-/output C / software user interface / hardware settings /
hardware detection / RAM/ROM error IO1 / RAM/ROM error
IO2 / Fieldbus / communication dsp-up / sensor driver /
uProc. / dsp / parameter frontend / application error / open
circuit A / open circuit B / open circuit C / over range A
(current) / over range B (current) / over range C (current) /
over range A (pulse) / over range B (pulse) / over range D
(pulse) / active settings / factory settings / backup 1 settings /
backup 2 settings / wiring A (output) / wiring B (output) /
wiring A (input) / wiring B (input) / flow exceeding limit / signal
lost path 1 / signal lost path 2 / signal lost path 3 / transducer
delay / temperature input / pressure input / p & T input / VoS
monitor
S:
S:
S:
S: out of specification / overflow counter 1 (C) / overflow
counter 1 (B) / overflow counter 2 / overflow counter 3 /
backplane invalid / error current A / error current B /
unreliable 1 / unreliable 2 / unreliable 3 / front end calibration
/ dsp timing error
C:
C:
C:
C:checks in progress / simulation flow / simulation VoS /
simulation fieldbus
I:
I:
I:
I: counter 1 stopped (C) / counter 1 stopped (B) / counter 2
stopped / counter 3 stopped / power fail / control input A
active / control input B active / over range display 1 / over
range display 2 / backplane sensor / backplane settings /
backplane difference / optical interface / write cycles overfl. /
baudrate search / no data exchange / start up
Current diagnosis
DISPLAY_CNFG
DISPLAY_CNFG
DISPLAY_CNFG
DISPLAY_CNFG
Display Configuration
Display Configuration
Display Configuration
Display Configuration
R/W
Select the function block output value to display at which line.
For details see subelements.
-
DISP_LINE1
Display Line 1
Setting:
AI1 / AI2 / AI3 / AI4 / AI5 / AI6 / PID / INT1 / INT2 / AR
AI1
DISP_LINE2
Display Line 2
AI2
DISP_LINE3
Display Line 3
AI3
ELECTRONIC_INFO
ELECTRONIC_INFO
ELECTRONIC_INFO
ELECTRONIC_INFO
Electronic Information
Electronic Information
Electronic Information
Electronic Information
R
Information about ident number, electronic revision and
production date. For details see subelements.
-
IDENT_NUMBER
Ident Number
Actual ident number
ELECTRONIC_REV
Electronic Revision
Actual electronic revision
PRODUCTION_DATE
Production Date
Date of production
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value