Operation – KROHNE GFC 300 FOUNDATION FIELDBUS User Manual
Page 26
4
OPERATION
26
GFC 300
www.krohne.com
07/2012 - 4001866001 - AD GFC 300 FF R01 en
Setting range for previous 2
parameters:
x_y_LIM
x_y_Limit
-3.39 E38…+3.39 E38 / - INF (- infinite) / + INF (+ infinite)
Setting for previous 2
parameters:
x_y_PRI
x_y_Priority
0: The associated alert may clear when the priority is changed
to 0, but it will never occur.
1: The associated alert is not send as a notification. If the
priority is above 1, then the alert must be reported.
2: Reserved for alerts that do not require the attention of a
plant operator, e.g. diagnostic and system alerts. Block alarm,
error alarm and update event have a fixed priority of 2.
3...7: Increasing higher priorities - advisory alarms.
8...15: Increasing higher priorities - critical alarms.
0
LOW_CUT
LOW_CUT
LOW_CUT
LOW_CUT
Low Cutoff
Low Cutoff
Low Cutoff
Low Cutoff
R/W
Limit used in square root processing. A value of zero percent
of scale is used in block processing if the transducer value
falls below this limit, in %of scale. This feature may be used to
eliminate noise near zero for a flow sensor.
0
Setting:
≥0.0
OUT
OUT
OUT
OUT
Output
Output
Output
Output
R/W
The primary analogue discrete value calculated as a result of
executing the function.
Note:
Note:
Note:
Note:
W = Writeable only by setting "OOS" in MODE_BLK
-
Status
R
Digital transducers, unlike their analogue versions, can detect
faults that make the measurement bad or prevent the
actuator from responding. This additional, valuable
information will be passed along with each transmission of a
data value in the form of a status attribute.
-
Value
R/W
A numerical quantity entered by a user or calculated by the
algorithm.
-
OUT_SCALE
OUT_SCALE
OUT_SCALE
OUT_SCALE
Output Scale
Output Scale
Output Scale
Output Scale
R/W
The high and low scale values, engineering units code and
number of digits to the right of the decimal point to be used in
displaying the OUT parameter and parameters which have the
same scaling as OUT.
-
EU_100
EU at 100%
R/W
The engineering unit value which represents the upper end of
range of the associated block parameter.
100.0
EU_0
EU at 0%
R/W
The engineering unit value which represents the lower end of
range of the associated block parameter.
0.0
Units Index
R/W
Device Description units code index for the engineering unit
descriptor for the associated block value.
Uninitialized
Setting:
All units are possible.
Decimal Point
R/W
The number of digits to the right of the decimal point which
should be used by an interface device in displaying the
specified parameter.
0
PV
PV
PV
PV
Process Value
Process Value
Process Value
Process Value
Either the primary analogue value for use in executing the
function or a process value associated with it.
-
Status
R
Digital transducers, unlike their analogue versions, can detect
faults that make the measurement bad or prevent the
actuator from responding. This additional, valuable
information will be passed along with each transmission of a
data value in the form of a status attribute.
0
Value
R
A numerical quantity entered by a user or calculated by the
algorithm.
0.0
PV_FTIME
PV_FTIME
PV_FTIME
PV_FTIME
PV F Time
PV F Time
PV F Time
PV F Time
(Process Value
(Process Value
(Process Value
(Process Value
Filter Time
Filter Time
Filter Time
Filter Time
Constant)
Constant)
Constant)
Constant)
R/W
Time constant of a single exponential filter for the PV, in
seconds.
0
Setting:
0.0…60.0
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value