beautypg.com

Operation – KROHNE GFC 300 FOUNDATION FIELDBUS User Manual

Page 26

background image

4

OPERATION

26

GFC 300

www.krohne.com

07/2012 - 4001866001 - AD GFC 300 FF R01 en

Setting range for previous 2

parameters:

x_y_LIM

x_y_Limit

-3.39 E38…+3.39 E38 / - INF (- infinite) / + INF (+ infinite)

Setting for previous 2

parameters:

x_y_PRI

x_y_Priority

0: The associated alert may clear when the priority is changed

to 0, but it will never occur.

1: The associated alert is not send as a notification. If the

priority is above 1, then the alert must be reported.

2: Reserved for alerts that do not require the attention of a

plant operator, e.g. diagnostic and system alerts. Block alarm,

error alarm and update event have a fixed priority of 2.

3...7: Increasing higher priorities - advisory alarms.

8...15: Increasing higher priorities - critical alarms.

0

LOW_CUT

LOW_CUT

LOW_CUT

LOW_CUT

Low Cutoff

Low Cutoff

Low Cutoff

Low Cutoff

R/W

Limit used in square root processing. A value of zero percent

of scale is used in block processing if the transducer value

falls below this limit, in %of scale. This feature may be used to

eliminate noise near zero for a flow sensor.

0

Setting:

≥0.0

OUT

OUT

OUT

OUT

Output

Output

Output

Output

R/W

The primary analogue discrete value calculated as a result of

executing the function.

Note:

Note:

Note:

Note:

W = Writeable only by setting "OOS" in MODE_BLK

-

Status

R

Digital transducers, unlike their analogue versions, can detect

faults that make the measurement bad or prevent the

actuator from responding. This additional, valuable

information will be passed along with each transmission of a

data value in the form of a status attribute.

-

Value

R/W

A numerical quantity entered by a user or calculated by the

algorithm.

-

OUT_SCALE

OUT_SCALE

OUT_SCALE

OUT_SCALE

Output Scale

Output Scale

Output Scale

Output Scale

R/W

The high and low scale values, engineering units code and

number of digits to the right of the decimal point to be used in

displaying the OUT parameter and parameters which have the

same scaling as OUT.

-

EU_100

EU at 100%

R/W

The engineering unit value which represents the upper end of

range of the associated block parameter.

100.0

EU_0

EU at 0%

R/W

The engineering unit value which represents the lower end of

range of the associated block parameter.

0.0

Units Index

R/W

Device Description units code index for the engineering unit

descriptor for the associated block value.

Uninitialized

Setting:

All units are possible.

Decimal Point

R/W

The number of digits to the right of the decimal point which

should be used by an interface device in displaying the

specified parameter.

0

PV

PV

PV

PV

Process Value

Process Value

Process Value

Process Value

Either the primary analogue value for use in executing the

function or a process value associated with it.

-

Status

R

Digital transducers, unlike their analogue versions, can detect

faults that make the measurement bad or prevent the

actuator from responding. This additional, valuable

information will be passed along with each transmission of a

data value in the form of a status attribute.

0

Value

R

A numerical quantity entered by a user or calculated by the

algorithm.

0.0

PV_FTIME

PV_FTIME

PV_FTIME

PV_FTIME

PV F Time

PV F Time

PV F Time

PV F Time

(Process Value

(Process Value

(Process Value

(Process Value

Filter Time

Filter Time

Filter Time

Filter Time

Constant)

Constant)

Constant)

Constant)

R/W

Time constant of a single exponential filter for the PV, in

seconds.

0

Setting:

0.0…60.0

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value