beautypg.com

Operation – KROHNE GFC 300 FOUNDATION FIELDBUS User Manual

Page 46

background image

4

OPERATION

46

GFC 300

www.krohne.com

07/2012 - 4001866001 - AD GFC 300 FF R01 en

4.6.3 Transducer Specification Block

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value

Alert Key

Alert Key

Alert Key

Alert Key

R/W

The identification number of the plant unit. This information

may be used in the host for sorting alarms, etc.

0

Setting:

1...255

BLOCK_ERR

BLOCK_ERR

BLOCK_ERR

BLOCK_ERR

Block Error

Block Error

Block Error

Block Error

R

This parameter reflects the error status associated with the

hardware or software components associated with a block. It

is a bit string, so that multiple errors may be shown.

Other

Setting:

Other: Non-specific error active

Block Configuration: Error detected in block configuration

Link Configuration: Error detected in link configuration

Simulation Active: Simulation enabled in this block

Local Override: Output tracking of faultstate active

Device Fault State: Device faultstate set

Device Maintenance: Device needs maintenance soon

Input Failure: Process variable has bad status

Output Failure: Failure detected in output hardware

Memory Failure: Memory error detected

Lost Static Data: Static parameters cannot be recovered

Lost NV Data: Non-volatile parameters cannot be recovered

Readback Check: Failure detected in READBACK

Maintenance Needed: Device NEEDS maintenance NOW

Power Up: Recovery from power failure

Out Of Service: Block actual mode is out of service

MODE_BLK

MODE_BLK

MODE_BLK

MODE_BLK

Block Mode

Block Mode

Block Mode

Block Mode

The actual, target, permitted and normal modes of the block.

-

TARGET

Target

R/W

This is the mode requested by the operator. Only one mode

from those allowed by the permitted mode parameter may be

requested.

Auto

Setting:

Auto / OOS

ACTUAL

Actual

R

This is the current mode of the block, which may differ from

the target based on operating conditions. Its value is

calculated as part of block execution.

Auto

Setting:

Auto / OOS

PERMITTED

Permitted

R/W

Defines the modes which are allowed for an instance of the

block. The permitted mode is configured based on application

requirement.

Auto

OOS

Setting:

Auto / OOS

NORMAL

Normal

R/W

This is the mode which the block should be set to during

normal operating conditions.

Auto

Setting:

Auto / OOS

ST_Rev

ST_Rev

ST_Rev

ST_Rev

Static Revision

Static Revision

Static Revision

Static Revision

R

The revision level of the static data associated with the

function block. The revision value will be incremented each

time a static parameter value in the block is changed.

0

Setting:

0...65535