ADIABATIC_INDEX

ADIABATIC_INDEX

ADIABATIC_INDEX

ADIABATIC_INDEX

adiabatic index

R/W

(Fct. C1.10)

14.000

Settings:

10.000…20.000

COUNTER_

COUNTER_

COUNTER_

COUNTER_

DECREASE

DECREASE

DECREASE

DECREASE

Counter Decrease

R/W

Plausibility counter decrement setting. Number of counts to

be decreased on the plausibility counter when the actual

measured value is within the error limits (Fct. C1.4.2).

1

Settings:

1...99

COUNTER_LIMIT

COUNTER_LIMIT

COUNTER_LIMIT

COUNTER_LIMIT

Counter Limit

R/W

Limit setting for the plausibility counter. When this limit is

reached, the measured value will not be discarded when it

exceeds the error limit (Fct. C1.4.3).

0

Settings:

0...999

DENSITY

DENSITY

DENSITY

DENSITY

Density

R/W

Density at normal condition, 0°C, 101325 Paa (Fct. C1.15).

1.00

Settings:

0.05...100.00

DYN_VISCOSITY

DYN_VISCOSITY

DYN_VISCOSITY

DYN_VISCOSITY

Dynamic Viscosity

R/W

Is only be used if "on" is selected in Fct. C1.9.1 (Fct. C1.9.2).

18.27

Settings:

0.50...50.00

ERROR_LIMIT

ERROR_LIMIT

ERROR_LIMIT

ERROR_LIMIT

Error Limit

R/W

In percentage of the measured value. If the measured value

exceeds this limit compared to the previous measured value,

the measured value will be discarded and the plausibility

counter will be increased (Fct. C1.4.1).

10.0

Settings:

0.0...100.00

FILTER

FILTER

FILTER

FILTER

Filter

R/W

(Fct. C1.3)

-

Limitation_Min

limitation min

R/W

Lower limitation of all flow values, before smoothing by time

constant, affects all outputs (Fct. C1.3.1).

-100.0

Settings:

-100.000…-0.001

Limitation_Max

limitation max

R/W

Upper limitation of all flow values, before smoothing by time

constant, affects all outputs (Fct. C1.3.1).

100.0

Settings:

0.001…100.000

Flow_Direction

flow direction

R/W

(Fct. C1.3.2)

normal

Settings:

normal / reverse

Time_Constant

time constant

R

Time constant on the Front End for flow-related

measurement (volume, mass, flow velocity) (Fct. C1.3.3).

0.25

Settings:

0.0...100.00

Low_Flow_Cutoff

lfc threshold

R/W

Low flow cutoff threshold process input (Fct. C1.3.4).

0.0

Settings:

0.0...10.00

Hysteresis

lfc hysteresis

R/W

Low flow cutoff hysteresis process input (Fct. C1.3.4).

0.0

Settings:

0.0...10.00

GFC_OPTION

GFC_OPTION

GFC_OPTION

GFC_OPTION

GFC option

R

Settings:

gas / steam

as ordered

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value