Operation – KROHNE GFC 300 FOUNDATION FIELDBUS User Manual
Page 43
OPERATION
4
43
GFC 300
www.krohne.com
07/2012 - 4001866001 - AD GFC 300 FF R01 en
Measurement_A
measurement
R
(Fct. C2.2.3)
pressure
Settings:
temperature / pressure / current input
Current_100
100% value
R
Current range 0%...100% for the selected measured variable
(Fct. C2.2.1).
20.0
Settings:
20.0…23.0
Current_0
0% value
R
Current range 0%...100% for the selected measured variable
(Fct. C2.2.1).
4.0
Settings:
0.5…4.0
Current_100ext
upper value
R/W
Exceeding the max. limit (Fct. C2.2.2).
21.0
Settings:
20.0…23.0
Current_0ext
lower value
R/W
Exceeding the min. limit (Fct. C2.2.2).
3.6
Settings:
0.5…4.0
RANGE_100
100% value
R/W
(Fct. C2.2.4)
250.0
Settings:
1.0…250.0
RANGE_0
0% value
R/W
(Fct. C2.2.4)
1.0
Settings:
1.0…250.0
Time_Constant
time constant
R/W
Averages measurement. Increasing value improves (Fct.
C2.2.5).
0.2
Settings:
0.0...100.00
Board_ID_No_IO
ID-No. board
R
I/O circuit board (Fct. C2.2.6)
SW_Ver_Build_No
software version
R
I/O circuit board (Fct. C2.2.6)
Product_Date_IO
production date
R
I/O circuit board (Fct. C2.2.6)
Sim_Value
simulation value
R/W
(Fct. C2.2.7)
1.0
Settings:
1.0…250.0
Sim_Set
simulation set
R/W
Settings:
disable / active
disable
Trimming_4mA
4mA trimming
R/W
Trimming of the current at 4 mA. Reset to 4 mA restores the
factory calibration (Fct. C2.2.8).
4.0
Settings:
3.6…5.5
Trimming_20mA
20mA trimming
R/W
Trimming of the current at 20 mA. Reset to 20 mA restores the
factory calibration (Fct. C2.2.9).
20.0
Settings:
18.5…21.5
CURRENT_IN_B
CURRENT_IN_B
CURRENT_IN_B
CURRENT_IN_B
current in B
current in B
current in B
current in B
R
(Fct. C2.3)
Measurement_B
measurement
R
(Fct. C2.3.3)
temperature
Settings:
temperature / pressure / current input
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value