OPERATION

4

43

GFC 300

www.krohne.com

07/2012 - 4001866001 - AD GFC 300 FF R01 en

Measurement_A

measurement

R

(Fct. C2.2.3)

pressure

Settings:

temperature / pressure / current input

Current_100

100% value

R

Current range 0%...100% for the selected measured variable

(Fct. C2.2.1).

20.0

Settings:

20.0…23.0

Current_0

0% value

R

Current range 0%...100% for the selected measured variable

(Fct. C2.2.1).

4.0

Settings:

0.5…4.0

Current_100ext

upper value

R/W

Exceeding the max. limit (Fct. C2.2.2).

21.0

Settings:

20.0…23.0

Current_0ext

lower value

R/W

Exceeding the min. limit (Fct. C2.2.2).

3.6

Settings:

0.5…4.0

RANGE_100

100% value

R/W

(Fct. C2.2.4)

250.0

Settings:

1.0…250.0

RANGE_0

0% value

R/W

(Fct. C2.2.4)

1.0

Settings:

1.0…250.0

Time_Constant

time constant

R/W

Averages measurement. Increasing value improves (Fct.

C2.2.5).

0.2

Settings:

0.0...100.00

Board_ID_No_IO

ID-No. board

R

I/O circuit board (Fct. C2.2.6)

SW_Ver_Build_No

software version

R

I/O circuit board (Fct. C2.2.6)

Product_Date_IO

production date

R

I/O circuit board (Fct. C2.2.6)

Sim_Value

simulation value

R/W

(Fct. C2.2.7)

1.0

Settings:

1.0…250.0

Sim_Set

simulation set

R/W

Settings:

disable / active

disable

Trimming_4mA

4mA trimming

R/W

Trimming of the current at 4 mA. Reset to 4 mA restores the

factory calibration (Fct. C2.2.8).

4.0

Settings:

3.6…5.5

Trimming_20mA

20mA trimming

R/W

Trimming of the current at 20 mA. Reset to 20 mA restores the

factory calibration (Fct. C2.2.9).

20.0

Settings:

18.5…21.5

CURRENT_IN_B

CURRENT_IN_B

CURRENT_IN_B

CURRENT_IN_B

current in B

current in B

current in B

current in B

R

(Fct. C2.3)

Measurement_B

measurement

R

(Fct. C2.3.3)

temperature

Settings:

temperature / pressure / current input

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value