beautypg.com

Operation – KROHNE GFC 300 FOUNDATION FIELDBUS User Manual

Page 11

background image

OPERATION

4

11

GFC 300

www.krohne.com

07/2012 - 4001866001 - AD GFC 300 FF R01 en

NORMAL

Normal

R/W

This is the mode which the block should be set to during

normal operating conditions.

Auto

Setting:

Auto / OOS

ST_REV

ST_REV

ST_REV

ST_REV

Static Revision

Static Revision

Static Revision

Static Revision

R

The revision level of the static data associated with the

function block. The revision value will be incremented each

time a static parameter value in the block is changed.

0 (=uninitialized)

Setting:

0...65535

STRATEGY

STRATEGY

STRATEGY

STRATEGY

Strategy

Strategy

Strategy

Strategy

R/W

The strategy field can be used to identify grouping of blocks.

This data is not checked or processed by the block.

0

Setting:

0...65535

TAG_DESC

TAG_DESC

TAG_DESC

TAG_DESC

Tag Description

Tag Description

Tag Description

Tag Description

R/W

The user description of the intended application of the block.

blanks

Setting:

≤32 digits

ACK_OPTION

ACK_OPTION

ACK_OPTION

ACK_OPTION

Acknowledge Option

Acknowledge Option

Acknowledge Option

Acknowledge Option

R/W

Selection of whether alarms associated with the function

block will be automatically acknowledged.

Uninitialized

Setting:

Disc Alm Auto Ack / Blk Alm Auto Ack / Fail Alm Auto Ack / Off

Spec Alm Auto Ack / Maint Alm Auto Ack / Check Alm Auto Ack

ALARM_SUM

ALARM_SUM

ALARM_SUM

ALARM_SUM

Alarm Summary

Alarm Summary

Alarm Summary

Alarm Summary

R

The current alert status, unacknowledged states, unreported

states and disabled states of the alarms associated with the

function block.

-

Current

R

The active status of each alarm.

Uninitialized

Setting:

Discrete Alarm / Block Alarm / Fail Alarm / Off Spec Alarm /

Maintenance Alarm / Check Alarm

Unacknowledged

R

The unacknowledged state of each alarm.

Uninitialized

Setting:

Disc Alm Unack / Block Alm Unack / Fail Alm Unack / Off Spec

Alm Unack / Maint Alm Unack / Check Alm Unack

Unreported

R

The unreported status of each alarm.

Uninitialized

Setting:

Disc Alm Unrep / Block Alm Unrep / Fail Alm Unrep / Off Spec

Alm Unrep / Maint Alm Unrep / Check Alm Unrep

Disabled

R/W

The disabled state of each alarm.

Uninitialized

Setting:

Disc Alm Disabled / Block Alm Disabled / Fail Alm Disabled /

Off Spec Alm Disabled / Maint Alm Disabled / Check Alm

Disabled

BLOCK_ALM

BLOCK_ALM

BLOCK_ALM

BLOCK_ALM

Block Alarm

Block Alarm

Block Alarm

Block Alarm

The block alarm is used for all configuration, hardware,

connection failure or system problems in the block. The cause

of the alert is entered in the subcode field. The first alert to

become active will set the "Active" status in the "Status"

attribute. As soon as the "Unreported" status is cleared by the

alert reporting task, another block alert may be reported

without clearing the "Active" status, if the subcode has

changed.

-

Unacknowledged

R/W

A discrete enumeration which is set to "Unacknowledged"

when an alarm occurs, and set to "Acknowledged" by a write

from a human interface device or other entity which can

acknowledge that the alarm/event has been noticed.

Uninitialized

Setting:

Uninitialized / Acknowledged / Unacknowledged

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value