Operation – KROHNE GFC 300 FOUNDATION FIELDBUS User Manual
Page 64
4
OPERATION
64
GFC 300
www.krohne.com
07/2012 - 4001866001 - AD GFC 300 FF R01 en
INTEG_OPTS
INTEG_OPTS
INTEG_OPTS
INTEG_OPTS
Integration Options
Integration Options
Integration Options
Integration Options
R/W
INTEG_OPTS is to be used to specify several integration
options as type of input used in each input, flow direction to be
considered in the totalization, status to be considered in the
totalization and if the totalization residue shall be used in the
next batch after a reset.
Uninitialized
The following INTEG_OPTS are possible (see also
INTEG_TYPE):
•
Input 1 accumulate: IN_1 is used as pulse (otherwise as rate)
•
Input 2 accumulate: IN_2 is used as pulse (otherwise as rate)
•
Flow forward: only positive net flow will be taken into
account for totalization
•
Flow reverse: only negative net flow will be taken into
account for totalization
•
Use Uncertain: IN_1 and IN_2 input will be taken into
account even if their states are "Uncertain" (otherwise the
value with the last "Good" status will be taken)
•
Use BAD Input: IN_1 or IN_2 with "Bad" status will be
interpreted as "Good" (Note: only the status is interpreted as
"Good", the value isn't used for totalization, but the good one,
i.e. RTOTAL isn't affected with this setting.
•
Carry: integration after a reset starts with the init value, but
with the residual after the trip value.
•
Add zero if Bad: if one of the input (IN_1 or IN_2) statuses are
"Bad", not the last "Good" value is used for totalization, but
zero (0).
•
Confirm reset: after a manual reset of totalization, the next
manual reset must be preceded by a reset confirmation by
the control system.
•
Generate reset event: in case of reset (automatic or manual),
an event notification will be sent to the control system.
(This function is an option and not supported.)
N_RESET
N_RESET
N_RESET
N_RESET
Number of Reset
Number of Reset
Number of Reset
Number of Reset
R
Counts the number of resets. It can not be written nor reset.
-
OP_CMD_INT
OP_CMD_INT
OP_CMD_INT
OP_CMD_INT
Operator
Operator
Operator
Operator
Command
Command
Command
Command
Integration
Integration
Integration
Integration
R/W
Operator command. "Reset" resets the totalizer.
Off
Setting:
0: Off / 1: Reset
OUT
OUT
OUT
OUT
Output
Output
Output
Output
R/W
The primary analog value calculated as a result of executing
the function. The display scaling for the corresponding output.
It has no effect on the block.
-
Status
R
Actual status of Output.
-
Value
R
Actual value
-
OUT_PTRIP
OUT_PTRIP
OUT_PTRIP
OUT_PTRIP
Output Pre Trip
Output Pre Trip
Output Pre Trip
Output Pre Trip
R/W
The second discrete output.
-
Status
R/W
Setting:
Good Non Cascade / Good Cascade / Uncertain / Bad Not
Connected / Bad
Bad Not Connected
Value
R/W
Setting:
0: Off / 1: On
Off
OUT_RANGE
OUT_RANGE
OUT_RANGE
OUT_RANGE
Output Range
Output Range
Output Range
Output Range
R/W
This is the display scaling for the output. It has no effect on the
block.
-
EU_100
Engineering Unit
100
R/W
The engineering unit value which represents the upper end of
range of the associated block parameter.
100.0
EU_0
Engineering Unit 0
R/W
The engineering unit value which represents the lower end of
range of the associated block parameter.
0.0
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value