Operation – KROHNE GFC 300 FOUNDATION FIELDBUS User Manual
Page 16
4
OPERATION
16
GFC 300
www.krohne.com
07/2012 - 4001866001 - AD GFC 300 FF R01 en
4.4.2 Manufacturer specific parameters of the signal converter for Resource Block
WRITE_LOCK
WRITE_LOCK
WRITE_LOCK
WRITE_LOCK
Write Lock
Write Lock
Write Lock
Write Lock
R/W
If set, no writes from anywhere are allowed, except to clear
WRITE_LOCK. Block inputs will continue to be updated.
Not locked
Setting:
Uninitialized / Not locked / Locked
WRITE_PRI
WRITE_PRI
WRITE_PRI
WRITE_PRI
Write Priority
Write Priority
Write Priority
Write Priority
R
Priority of the alarm generated by clearing the write lock.
0
Setting:
0...15
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value
DEV_DESCRIPTION
DEV_DESCRIPTION
DEV_DESCRIPTION
DEV_DESCRIPTION
Device Description
Device Description
Device Description
Device Description
R
Describes some characteristics of the device.
-
DB_DEVICE
Data Base GDC
R
Data base version of the GDC device.
Current data base
version
C_NUMBER_DEVICE
C-Number Device
R
Current C-Number of this device.
Current C-Number
of device
C_NUMBER_
PRODUCT
C-Number Production
R
C-Number of production; this number identifies the type of
electronics, can be found on the signal converter assembly
sticker as well.
Current C-Number
of production
CONVERTER_MODEL
Converter Model
R
The model of signal converter.
GFC300
LOGICAL_PLACE
Logical Place
R
Setting:
Error / Standard / Extended standard / Special
Standard
SUPPLY_OPTION
Supply Option
R
Supply of sensor and electronics option.
As ordered
Setting:
Configuration error / Unknown / 100…230 VAC / 12...24 VDC /
24 VAC/DC
DISPLAY_OPTION
Display Option
R
Setting:
Configuration error or missing / Standard / Eastern Europe /
Northern Europe / Southern Europe / Far East / Japanese /
Chinese / Russian
As ordered
IO_SELECTION
IO1 Modular IO
R
Setting:
Configuration error or missing / Foundation Fieldbus
Foundation
Fieldbus
IO_MODULE_A
IO2 Module Term. A
R
Setting:
Configuration error or missing / Without carrier / Exi
Opt.:Current Out act + PO/CI pas / Exi Opt. : CurrOut pas +
PO/CI pas / Exi Opt.2 : CurrIn act + PO/CI pas / Exi Opt.2 :
CurrIn pas + PO/CI pas / Exi Opt.3 : 2x CurrIn act
-
IO_MODULE_B
IO Module Term. B
R
Not used.
-
DIAGNOSIS
DIAGNOSIS
DIAGNOSIS
DIAGNOSIS
Diagnosis
Diagnosis
Diagnosis
Diagnosis
R
Detailed diagnosis of the device.
-
MEMORY_SUMMARY
Memory Summary
R
Summary of self diagnosis.
ok
Setting:
ok / bit 8…15 not used / EEPROM / FRAM / FLASH / ROM
application / ROM boot area / RAM ext / RAM int / Task Control
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value