background image

4

OPERATION

24

GFC 300

www.krohne.com

07/2012 - 4001866001 - AD GFC 300 FF R01 en

FIELD_VAL

FIELD_VAL

FIELD_VAL

FIELD_VAL

Field Value

Field Value

Field Value

Field Value

R

Raw value of the field device in percent of the PV range, with a

status reflecting the transducer condition, before signal

characterization (L_TYPE) or filtering (PV_FTIME).

-

Status

R

Digital transducers, unlike their analogue versions, can detect

faults that make the measurement bad or prevent the

actuator from responding. This additional, valuable

information will be passed along with each transmission of a

data value in the form of a status attribute.

Bad

Non Specific

Not Limited

Value

R

A numerical quantity entered by a user or calculated by the

algorithm.

0.0

GRANT_DENY

GRANT_DENY

GRANT_DENY

GRANT_DENY

Grant Deny

Grant Deny

Grant Deny

Grant Deny

Options for controlling access of host computers and local

control panels to operating, tuning and alarm parameters of

the block.

-

GRANT

Grant

R/W

Depending on the philosophy of the plant, the operator or a

higher level device (HLD) or a local operator's panel (LOP) in

the case of "Local", may turn on an item of the "Grant"

attribute - "Program, Tune, Alarm or Local".

Uninitialized

Setting:

Program / Tune / Alarm / Local / Operate

DENY

Deny

R/W

The deny attribute is provided for use by a monitoring

application in an interface device and may not be changed by

an operator.

Uninitialized

Setting:

Program denied / Tune denied / Alarm denied / Local denied /

Operate denied

HI_ALM

HI_ALM

HI_ALM

HI_ALM

High Alarm

High Alarm

High Alarm

High Alarm

The status for High Alarm and its associated time stamp.

Settings of 5 subelements see in the following part.

-

HI_HI_ALM

HI_HI_ALM

HI_HI_ALM

HI_HI_ALM

High High Alarm

High High Alarm

High High Alarm

High High Alarm

Mix

The status for High High Alarm and its associated time stamp.

Settings of 5 subelements see in the following part.

-

Settings of 5 subelements for previous 2 parameters High Alarm and High High Alarm:

Unacknowledged

R/W

Setting:

Uninitialized / Acknowledged / Unacknowledged

Uninitialized

Alarm State

R

Setting:

Uninitialized / Clear - reported / Clear - not reported / Active -

reported / Active - not reported

Uninitialized

Time Stamp

R

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

Uninitialized

Subcode

R

Setting:

Other / Block Configuration / Link Configuration / Simulation

Active / Local Override / Device Fault State / Device

Maintenance / Input Failure / Output Failure / Memory

Failure / Lost Static Data / Lost NV Data / Readback Check /

Maintenance Needed / Power Up / Out Of Service

Other

Value

R

A numerical quantity entered by a user or calculated by the

algorithm.

0.0

HI_HI_LIM

HI_HI_LIM

HI_HI_LIM

HI_HI_LIM

High High Limit

High High Limit

High High Limit

High High Limit

R/W

The setting for High High Alarm in engineering units.

Setting range see in the following part.

NaN

HI_HI_PRI

HI_HI_PRI

HI_HI_PRI

HI_HI_PRI

High High Priority

High High Priority

High High Priority

High High Priority

R/W

Priority of the High High Alarm.

Setting see in the following part.

0

HI_LIM

HI_LIM

HI_LIM

HI_LIM

High Limit

High Limit

High Limit

High Limit

R/W

The setting for High Alarm in engineering units.

Setting range see in the following part.

NaN

HI_PRI

HI_PRI

HI_PRI

HI_PRI

High Priority

High Priority

High Priority

High Priority

R/W

Priority of the High Alarm.

Setting see in the following part.

0

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value