background image

4

OPERATION

44

GFC 300

www.krohne.com

07/2012 - 4001866001 - AD GFC 300 FF R01 en

Current_100

100% value

R

Current range 0%...100% for the selected measured variable

(Fct. C2.3.1).

20.0

Settings:

20.0…23.0

Current_0

0% value

R

Current range 0%...100% for the selected measured variable

(Fct. C2.3.1).

4.0

Settings:

0.5…4.0

Current_100ext

upper value

R/W

Exceeding the max. limit (Fct. C2.3.2).

21.0

Settings:

20.0…23.0

Current_0ext

lower value

R/W

Exceeding the min. limit (Fct. C2.3.2).

3.6

Settings:

0.5…4.0

RANGE_100

100% value

R/W

(Fct. C2.3.4)

800.0

Settings:

-40.0…800.0

RANGE_0

0% value

R/W

(Fct. C2.3.4)

-40.0

Settings:

-40.0…800.0

Time_Constant

time constant

R/W

Averages measurement. Increasing value improves (Fct.

C2.3.5).

0.2

Settings:

0.2...100.00

Board_ID_No_IO

ID-No. board

R

I/O circuit board (Fct. C2.3.6)

SW_Ver_Build_No

software version

R

I/O circuit board (Fct. C2.3.6)

Product_Date_IO

production date

R

I/O circuit board (Fct. C2.3.6)

Sim_Value

simulation value

R/W

(Fct. C2.3.7)

20.0

Settings:

-40.0…800.0

Sim_Set

simulation set

R/W

Settings:

disable / active

disable

Trimming_4mA

4mA trimming

R/W

Trimming of the current at 4 mA. Reset to 4 mA restores the

factory calibration (Fct. C2.3.8).

4.0

Settings:

3.6…5.5

Trimming_20mA

20mA trimming

R/W

Trimming of the current at 20 mA. Reset to 20 mA restores the

factory calibration (Fct. C2.3.9).

20.0

Settings:

18.5…21.5

GFC_OPTION

GFC_OPTION

GFC_OPTION

GFC_OPTION

GFC option

R

Settings:

gas / steam

as ordered

P_T_CORRECTION

P_T_CORRECTION

P_T_CORRECTION

P_T_CORRECTION

P & T correction

R/W

For device display only: compensation for thermal and

pressure expansion of the sensor (Fct. C1.11).

Normal

Settings:

none / Normal / Old Normal / IUPAC / OPEC

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value