Operation – KROHNE GFC 300 FOUNDATION FIELDBUS User Manual
Page 44
4
OPERATION
44
GFC 300
www.krohne.com
07/2012 - 4001866001 - AD GFC 300 FF R01 en
Current_100
100% value
R
Current range 0%...100% for the selected measured variable
(Fct. C2.3.1).
20.0
Settings:
20.0…23.0
Current_0
0% value
R
Current range 0%...100% for the selected measured variable
(Fct. C2.3.1).
4.0
Settings:
0.5…4.0
Current_100ext
upper value
R/W
Exceeding the max. limit (Fct. C2.3.2).
21.0
Settings:
20.0…23.0
Current_0ext
lower value
R/W
Exceeding the min. limit (Fct. C2.3.2).
3.6
Settings:
0.5…4.0
RANGE_100
100% value
R/W
(Fct. C2.3.4)
800.0
Settings:
-40.0…800.0
RANGE_0
0% value
R/W
(Fct. C2.3.4)
-40.0
Settings:
-40.0…800.0
Time_Constant
time constant
R/W
Averages measurement. Increasing value improves (Fct.
C2.3.5).
0.2
Settings:
0.2...100.00
Board_ID_No_IO
ID-No. board
R
I/O circuit board (Fct. C2.3.6)
SW_Ver_Build_No
software version
R
I/O circuit board (Fct. C2.3.6)
Product_Date_IO
production date
R
I/O circuit board (Fct. C2.3.6)
Sim_Value
simulation value
R/W
(Fct. C2.3.7)
20.0
Settings:
-40.0…800.0
Sim_Set
simulation set
R/W
Settings:
disable / active
disable
Trimming_4mA
4mA trimming
R/W
Trimming of the current at 4 mA. Reset to 4 mA restores the
factory calibration (Fct. C2.3.8).
4.0
Settings:
3.6…5.5
Trimming_20mA
20mA trimming
R/W
Trimming of the current at 20 mA. Reset to 20 mA restores the
factory calibration (Fct. C2.3.9).
20.0
Settings:
18.5…21.5
GFC_OPTION
GFC_OPTION
GFC_OPTION
GFC_OPTION
GFC option
R
Settings:
gas / steam
as ordered
P_T_CORRECTION
P_T_CORRECTION
P_T_CORRECTION
P_T_CORRECTION
P & T correction
R/W
For device display only: compensation for thermal and
pressure expansion of the sensor (Fct. C1.11).
Normal
Settings:
none / Normal / Old Normal / IUPAC / OPEC
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value