VISOR ALARM – ARLY Configuration
II - 66
Doc.DM359-I
Rev.2.0
ARLY-1 Cfg>USER-DEFINED-EVENTS HDW-FAULT 300
ARLY-1 Cfg>
To return to the default configuration for this parameter, use the following command.
ARLY-1 Cfg>NO USER-DEFINED-EVENTS HDW-FAULT
q) USER-DEFINED-EVENTS MIP-HW-FAILURE
The IP Module accomplishes hardware supervision of its main critical modules (CPU, CMX, etc.). If a
failure is detected, the IP Module sends an alarm which, by default, the VisorALARM interprets with
the CONTACT-ID 333 code (expansion module failure).
Syntax:
ARLY-1 Cfg>USER-DEFINED-EVENTS MIP-HW-FAILURE
ARLY-1 Cfg>
Example:
ARLY-1 Cfg>USER-DEFINED-EVENTS MIP-HW-FAILURE 333
ARLY-1 Cfg>
To return to the default configuration for this parameter, use the following command.
ARLY-1 Cfg>NO USER-DEFINED-EVENTS MIP-HW-FAILURE
r) USER-DEFINED-EVENTS VISORALARM-TIME-INACCURATE
The VisorALARM clock must be synchronized with an NTP server in order to guarantee time
accuracy. This command permits you to configure the event code to be sent in the alarm generated by
the VisorALARM when no NTP client configuration is detected or communication with the
configured NTP server fails. The default code for this alarm is 626 (time/date inaccurate).
Syntax:
ARLY-1 Cfg>USER-DEFINED-EVENTS VISORALARM-TIME-INACCURATE
ARLY-1 Cfg>
Example:
ARLY-1 Cfg>USER-DEFINED-EVENTS VISORALARM-TIME-INACCURATE 626
ARLY-1 Cfg>
To return to the default configuration for this parameter, use the following command.
ARLY-1 Cfg>NO USER-DEFINED-EVENTS VISORALARM-TIME-INACCURATE
s) USER-DEFINED-EVENTS AC-LOSS
Permits you to configure the event code to be sent in the alarm generated by the VisorALARM when
an AC power loss (voltage under 10.2 V) is detected through the activation of the VisorALARM’s
general purpose input configured for this purpose by the UPS (Uninterruptible Power Supply). By
default the alarm code is 301 (AC loss).
Syntax:
ARLY-1 Cfg>USER-DEFINED-EVENTS AC-LOSS
ARLY-1 Cfg>
Example: