Serial-parameters – SilentKnight VisorAlarm ARLY Interface User Manual
Page 54

VISOR ALARM – ARLY Configuration
II - 49
Doc.DM359-I
Rev.2.0
The default configuration for this parameter is Contact-ID.
2.14. SERIAL-PARAMETERS
Permits you to configure the asynchronous serial connection parameters used to connect the
VisorALARM to the Automation Sw. These parameters refer to the line speed, n data bits, stop bits,
etc.
Syntax:
ARLY-1 Cfg>SERIAL-PARAMETERS parameter parameter_value
data-bits
parity
speed
stop-bits
a) SERIAL-PARAMETERS DATA-BITS
Establishes the number of data bits. The available values are 5, 6, 7, and 8. Default is 8.
Syntax:
ARLY-1 Cfg>SERIAL-PARAMETERS DATA-BITS number_data_bits
Example:
ARLY-1 Cfg>SERIAL-PARAMETERS DATA-BITS 7
ARLY-1 Cfg>
b) SERIAL-PARAMETERS PARITY
Establishes the type of parity used. The available values are as follows:
EVEN: EVEN parity.
MARK: MARK parity.
NONE: No parity used.
ODD: ODD parity.
SPACE: SPACE parity
Default is NONE.
Syntax:
ARLY-1 Cfg>SERIAL-PARAMETERS PARITY parity_type
EVEN
MARK
NONE
ODD
SPACE
Example:
ARLY-1 Cfg>SERIAL-PARAMETERS PARITY EVEN
ARLY-1 Cfg>
c) SERIAL-PARAMETERS SPEED
Establishes the transmission / reception speed in the serial line (in bits/s). The available values are
between 300 and 64000 bps. Default is 9600 bps.
Syntax:
ARLY-1 Cfg>SERIAL-PARAMETERS SPEED speed
Example: