VISOR ALARM – ARLY Configuration

II - 65

Doc.DM359-I

Rev.2.0

To return to the default configuration for this parameter, use the following command.

ARLY-1 Cfg>NO USER-DEFINED-EVENTS PSTN-FAILURE

n) USER-DEFINED-EVENTS MIP-CHANGED
Permits you to configure the event code to be sent in the alarm generated by the VisorALARM when
a change in the Serial Number of a registered IP Module occurs, i.e. whenever an IP Module is
replaced by other unit. By default the alarm code is 306 (panel programming changed).
Syntax:

ARLY-1 Cfg>USER-DEFINED-EVENTS MIP-CHANGED
ARLY-1 Cfg>

Example:

ARLY-1 Cfg>USER-DEFINED-EVENTS MIP-CHANGED 306
ARLY-1 Cfg>


To return to the default configuration for this parameter, use the following command.

ARLY-1 Cfg>NO USER-DEFINED-EVENTS MIP-CHANGED

o) USER-DEFINED-EVENTS ICMP-POLL-FAILURE
The VisorALARM supervises the state of activity of each registered IP Module by sending ICMP
packets and listening to the response. Whenever a device fails to respond to the ICMP polling, the
VisorALARM sends an alarm which, by default, is assigned CONTACT-ID 330 code (system
peripheral trouble
).
Syntax:

ARLY-1 Cfg>USER-DEFINED-EVENTS ICMP-POLL-FAILURE
ARLY-1 Cfg>

Example:

ARLY-1 Cfg>USER-DEFINED-EVENTS ICMP-POLL-FAILURE 330
ARLY-1 Cfg>


To return to the default configuration for this parameter, use the following command.

ARLY-1 Cfg>NO USER-DEFINED-EVENTS ICMP-POLL-FAILURE

p) USER-DEFINED-EVENTS HDW-FAULT
Permits you to configure the event code to be sent in the alarm generated by the VisorALARM when
a supervised hardware element faults. By default the alarm code is 300 (system trouble) and the zone
number allows the user to identify the specific hardware element which caused the fault:

• Zone 0: Cooling Fan 1.
• Zone 1: Cooling Fan 2.
• Zone 2: Liquid Crystal Display.
• Zone 3: Buzzer.
• Zone 4: Printer.

Syntax:

ARLY-1 Cfg>USER-DEFINED-EVENTS HDW-FAULT
ARLY-1 Cfg>

Example: