SilentKnight VisorAlarm ARLY Interface User Manual
Page 62

VISOR ALARM – ARLY Configuration
II - 57
Doc.DM359-I
Rev.2.0
9.
Example:
ARLY-1 Cfg>UPDATE MIP 101234 BCK-KEEP-ALIVE-RETRIES-TIMER 3
ARLY-1 Cfg
>
To return to the default configuration for this parameter, use the following command.
ARLY-1 Cfg>NO UPDATE MIP accnt BCK-KEEP-ALIVE-RETRIES-TIMER time
p) UPDATE MIP accnt RESET
Resets the mIP/IPDACT whose account number has been provided.
Syntax:
ARLY-1 Cfg>UPDATE MIP accnt RESET
Example:
ARLY-1 Cfg>UPDATE MIP 101234 RESET
ARLY-1 Cfg>
q) UPDATE MIP accnt LOCAL-EVENTS-ZONE
Only available for mIP/IPDACT command.
r) UPDATE MIP accnt MNT-IP-ADDRESS
This parameter defines the address of the maintenance receiver that must receive the “Maintenance
Signals”. “Maintenance signals” are those “System Trouble” signals or “Communication Trouble”
signals of a mIP device that must be sent to an alternate site in order to perform an specialized
management of the problems.
Syntax:
ARLY-1 Cfg>MIP accnt mnt-ip-address ip-address
IP-address
IP Address of the Maintenance VisorALARM.
Example:
ARLY-1 Cfg>MIP 77889900 MNT-IP-ADDRESS 80.16.90.104
ARLY-1 Cfg>
To return to the default configuration for this parameter, use the following command.
ARLY-1 Cfg>NO MIP accnt MNT-IP-ADDRESS ip-address
s) UPDATE MIP accnt MNT-PASSWORD
This parameter is the encryption keyword for the Maintenance VisorALARM messages. This
keyword can depend on the mIP/IPDACT account number as with any other password.
Syntax:
ARLY-1 Cfg>MIP accnt MNT-PASSWORD password
Password
Password of up to 16 hexadecimal digits (0 to 9, A, B, C, D, E and F).