A1.6 mao function block, A1.6, A-15 – Yokogawa Multi Channel Oxygen Analyzer System ZR22/AV550G User Manual
Page 64

A-15
IM 11M12D01-61E
A1.6 MAO Function Block
Relative
Index
Index Parameter Name
Factory Default
Write Mode
Explanation
0
10000 Block Header
TAG: “MAO1”
Block Tag =
O/S
Information on this block such as Block Tag, DD Revision,
and Execution.
1
10001 ST_REV
–
–
Represents the revision level of setting parameters
associated with the MAO block. Changing the setpoint
updates this revision. Used, for example, to check for
parameter changes.
2
10002 TAG_DESC
(Spaces)
AUTO
A universal parameter used to store comments on tag
contents. 32 characters maximum.
3
10003 STRATEGY
1
AUTO
A universal parameter used specifically when the host
system distinguishes one function block from another.
4
10004 ALERT_KEY
1
AUTO
Key information used to identify the place where the alert in
question has been issued. Under normal conditions, this
parameter is used so that the host system localizes the
place to a specific area within the plant targeted by a
specific operator and selects only necessary alerts. One of
the universal parameters.
5
10005 MODE_BLK
AUTO
AUTO
A universal parameter used to represent the block’s
operating status. This parameter consists of Actual, Target,
Permit, and Normal modes.
6
10006 BLOCK_ERR
0
–
Denotes the error status related to the local block.
7
10007 CHANNEL
7
O/S
Used to set the channel number of the hardware to be
coupled with the transducer block. This parameter is fixed
to 7 for the AV550G.
8
10008 IN_1
–
MAN
Denotes the input value and status.
9
10009 IN_2
–
MAN
Denotes the input value and status.
10
10010 IN_3
–
MAN
Denotes the input value and status.
11
10011 IN_4
–
MAN
Denotes the input value and status.
12
10012 IN_5
–
MAN
Denotes the input value and status.
13
10013 IN_6
–
MAN
Denotes the input value and status.
14
10014 IN_7
–
MAN
Denotes the input value and status.
15
10015 IN_8
–
MAN
Denotes the input value and status.
16
10016 MO_OPTS
0
AUTO
Sets the method for processing the values of IN_1 to IN_8.
17
10017 FSTATE_TIME
0
AUTO
Denotes the time taken from when any of IN_1 to IN_8 fails
to when the block falls into a fault state (unit: sec).
18
10018 FSTATE_VAL1
0
AUTO
A value to be stored as the value of IN_1 when IN_1 falls
into a fault state.
19
10019 FSTATE_VAL2
0
AUTO
A value to be stored as the value of IN_1 when IN_2 falls
into a fault state.
20
10020 FSTATE_VAL3
0
AUTO
A value to be stored as the value of IN_1 when IN_3 falls
into a fault state.
21
10021 FSTATE_VAL4
0
AUTO
A value to be stored as the value of IN_1 when IN_4 falls
into a fault state.
22
10022 FSTATE_VAL5
0
AUTO
A value to be stored as the value of IN_1 when IN_5 falls
into a fault state.
23
10023 FSTATE_VAL6
0
AUTO
A value to be stored as the value of IN_1 when IN_6 falls
into a fault state.
24
10024 FSTATE_VAL7
0
AUTO
A value to be stored as the value of IN_1 when IN_7 falls
into a fault state.
25
10025 FSTATE_VAL8
0
AUTO
A value to be stored as the value of IN_1 when IN_8 falls
into a fault state.
26
10026 FSTATE_STATUS
0
–
Shows whether any of IN_1 to IN_8 is in a fault state.
27
10027 UPDATE_EVT
–
–
Shows details on an update event that has occurred.
28
10028 BLOCK_ALM
–
–
Shows details of an error that has occurred within the
block.
Appe 1-6.ai