beautypg.com

View objects -10, 3 view objects – Yokogawa Multi Channel Oxygen Analyzer System ZR22/AV550G User Manual

Page 29

background image

<5. CONFIGURATION>

5-10

IM 11M12D01-61E

5.6.3 View Objects

View objects are used to group parameters. This reduces the load of data transactions. Each AV550G

supports four view objects for each resource block, transducer block, each of the three AI blocks, two

DI blocks, MAI and MAO blocks.
Each view object contains a group of the parameters listed in Tables 5.11 to 5.14.
Table 5.10 Purpose of Each View Object

Table 5.11 View Objects for Resource Block

1

ST_REV

2

2

2

2

2

TAG_DESC

3

STRATEGY

2

4

ALERT_KEY

1

5

MODE_BLK

4

4

6

BLOCK_ERR

2

2

7

RS_STATE

1

1

8

TEST_RW

9

DD_RESOURCE

10

MANUFAC_ID

4

11

DEV_TYPE

2

12

DEV_REV

1

13

DD_REV

1

14

GRANT_DENY

2

15

HARD_TYPES

2

16

RESTART

17

FEATURES

2

18

FEATURE_SEL

2

19

CYCLE_TYPE

1

20

CYCLE_SEL

1

21

MIN_CYCLE_T

4

22

MEMORY_SIZE

2

23

NV_CYCLE_T

4

24

FREE_SPACE

4

25

FREE_TIME

4

4

26

SHED_RCAS

4

27

SHED_ROUT

4

28

FAIL_SAFE

1

1

29

SET_FSAFE

30

CLR_FSAFE

T0511.ai

Relative

Index

Parameter Mnemonic VIEW

1

VIEW

2

VIEW

3

VIEW

4

Relative

Index

Parameter Mnemonic VIEW

1

VIEW

2

VIEW

3

VIEW

4

31

MAX_NOTIFY

4

32

LIM_NOTIFY

4

33

CONFIRM_TIME

4

34

WRITE_LOCK

1

35

UPDATE_EVT

36

BLOCK_ALM

37

ALARM_SUM

8

8

38

ACK_OPTION

2

39

WRITE_PRI

1

40

WRITE_ALM

41

ITK_VER

42

SOFT_REV

43

SOFT_DESC

44

SIM_ENABLE_MSG

45

DEVICE_STATUS_1

4

46

DEVICE_STATUS_2

4

47

DEVICE_STATUS_3

4

48

DEVICE_STATUS_4

4

49

DEVICE_STATUS_5

4

50

DEVICE_STATUS_6

4

51

DEVICE_STATUS_7

4

52

DEVICE_STATUS_8

4

Total bytes

53
54
55
56
57
58

SOFTDWN_PROTECT
SOFTDWN_FORMAT
SOFTDWN_COUNT
SOFTDWN_ACT_AREA
SOFTDWN_MOD_REV
SOFTDWN_PROTECT

1
1
2

1
16
2

22 30 73 35

VIEW_1

VIEW_2

VIEW_3

VIEW_4

Set of all the dynamic parameters.

Description

Set of dynamic parameters required by operator for plant

operation. (PV, SV, OUT, Mode etc.)

Set of static parameters which need to be shown to plant

operator at once. (Range etc.)

Set of static parameters for configuration or maintenance.

T0510.ai