Yokogawa AXFA14G/C User Manual
Page 69

IM 01E20F12-01E
9-11
9. PARAMETER LISTS
T0904-2.EPS
Index
Parameter
Valid Range
Initial Value
Description
Write
Mode
32
PRESET_TOT
This parameter is used in order to define the starting value to the
totalizer.
Auto
-99999999 to
+99999999
0 or larger
0.000
33
ALARM_HYS
Amount the PV must return within the alarm limits before the alarm
condition clears. Alarm Hysteresis is expressed as a percent of the
PV span.
Auto
0.000
34
HI_HI_LIM
The setting for high high alarm in engineering units.
The setting for high alarm in engineering units.
The setting of the low alarm in engineering units.
The setting of the low low alarm in engineering units.
Auto
max. Value
+INF
35
HI_LIM
Auto
max. Value
+INF
36
LO_LIM
Auto
min. Value
-INF
37
LO_LO_LIM
Auto
min. Value
-INF
This parameter is used in order to set the state of the upper limit of
alarms.
This parameter contains the state of the upper limit of an alarm and
the related time stamp. The time stamp expresses the time the
measured variable has been equal or higher than the upper limit of
the alarm.
38
HI_HI_ALM
(DS-39)
–
0
Unacknow-
ledged
–
0
Alarm State
0: No alarm
Alarm active
exclude 0
–
0
Time_Stamp
–
0
Subcode
–
0
Value
This parameter is used in order to set the state of the upper limit of
warnings.
This parameter contains the state of the upper limit of a warning and
the related time stamp. The time stamp expresses the time the
measured variable has been equal or higher than the upper limit of
the warning.
39
HI_ALM
(DS-39)
–
0
Unacknow-
ledged
–
0
Alarm State
0: No alarm
Alarm active
exclude 0
–
0
Time_Stamp
–
0
Subcode
–
0
Value
This parameter is used in order to set the state of the lower limit of
warnings.
This parameter contains the state of the lower limit of a warning and
the related time stamp. The time stamp expresses the time at which
the measured variable has been equal to or lower than the lower
limit of the warning.
40
LO_ALM
(DS-39)
–
0
Unacknow-
ledged
–
0
Alarm State
0: No alarm
Alarm active
exclude 0
–
0
Time_Stamp
–
0
Subcode
–
0
Value
This parameter is used in order to set the state of the lower limit of
alarms.
This parameter contains the state of the lower limit of an alarm and
the related time stamp. The time stamp expresses the time at which
the measured variable has been equal to or lower than the lower
limit of the alarm.
41
LO_LO_ALM
(DS-39)
–
0
Unacknow-
ledged
–
0
Alarm State
0:No alarm
Alarm active
exclude 0
–
0
Time_Stamp
–
0
Subcode
–
0
Value
For commissioning and test purposes the input value from the
Transducer Block in the Totalizer Function Block, TOT-FB can be
modified when the hardware simulation jumper is on. That means
that the Transducer and TOT-FB will be disconnected.
52
SIMULATE
(DS-50)
42-51 reserved by PNO
0
Simulate_
Status
Auto
View objects allow the following groups of physical block parameter
values to be read with one read request.
ST_REV, MODE_BLK, ALARM_SUM, TOTAL
53
VIEW_TOTALIZER_FB
–
Auto
0
Simulate_
Value
Auto
0: Disabled,
Enable exclude 0
0: Disabled
Simulate_
Enabled