7.
DIAGNOSTIC INFORMATION
7.1 DEVICE STATUS
Diagnostic information and failures of the AXF are indicated by using parameter DIAGNOSIS (slot 0, index 29) and
DIAGNOSIS_EXTENSION (slot:0, index 30) in Physical Block. Each diagnostic information is supported when the
corresponding bit in DIAGNOSIS_MASK and DIAGNOSIS_EXTENSION is set. Diagnosis and Diagnosis Extension
are listed in Table 7.1 and Table 7.2.
Table 7.1
Contents of DIAGNOSIS
T0701.EPS
1
0
DIA_HW_ELECTR
Hardware failure of the electronic
10:uP Fault
1
17:Comm uP Fault
19:I/F Module Fault
12:A/D(H) Fault
13:A/D(L) Fault
14:A/D(Z) Fault
100:Comm uP Fault
105:Comm Error1
106:Comm Error2
1
DIA_HW_MECH
Hardware failure mechanics
15:Coil Open
1
2
DIA_TEMP_MOTOR
Motor temperature too high
–
0
3
DIA_TEMP_ELECTR
Electronic temperature too high
–
0
4
DIA_MEM_CHKSUM
Memory error
11:EEPROM Fault
1
101:Comm EEPROM Fault
5
DIA_MEASUREMENT
Failure in Measurement
30:Sig Overflow
1
6
DIA_NOT_INIT
Device not initialized (No self calibration)
16:EEPROM Dflt
1
7
DIA_INIT_ERR
Self calibration failed
–
0
2
0
DIA_ZERRO_ERR
Zero point error (limit position)
82:Auto Zero Wng
1
1
DIA_SUPPLY
1 DIA_SUPPLY Power supply failed
–
0
(electrical, pneumatic)
2
DIA_CONF_INVAL
Configuration not valid
50:Span > 10m/s
1
51:Span < 0.1m/s
57:Dens Set Err
71:Meas Mod Set
72:Size Set Err
73:Adh Set Err
3
DIA_WARMSTART
New-start-up (warm start up) carried out.
hot start
0
4
DIA_COLDSTART
Re-start-up (cold start up) carried out.
HW,SW,DL restart power fail
0
5
DIA_MAINTENANCE
Maintenance required
31:Empty Pipe
1
33:Adhesion Alm
80:Adhesion Wng
85:Flow Vel Over
6 DIA_CHARACT
Characterization
invalid
–
0
7
IDENT_NUMBER_Violation
Set to 1 (one), if the Ident_Number of the running
1
cyclic data transfer and the value of Physical Block
IDENT_NUMBER_SELECTOR parameter are different.
3
0-7
Reserved
Reserved for use within the PNO
X
4
0-6
Reserved
Reserved for use within the PNO
X
7
EXTENSION_AVAILABLE
More diagnosis information is available.
1
Octet
Mnemonic
Description