9. PARAMETER LISTS

9.3

Transducer Block Parameter List (Slot 7)

T0903-1.EPS

Index

Parameter

Valid Range

Initial Value

Description

Write

Mode

16

BLOCK_OBJECT
(DS-32)

Information on this block such as Block Tag, DD Revision, Execution
Time etc.

17

ST_REV

0

The revision level of the static data associated with the function
block. The revision value will be incremented each time a static
parameter value in the block is changed.

18

TAG_DESC

Auto

The user description of the intended application of the block.

19

STRATEGY

Auto

0 to 65535

0

The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.

20

ALERT_KEY

Auto

0 to 255

0

The identification number of the plant unit. This information may be
used in the host for sorting alarms, etc.

21

TARGET_MODE

Auto

The permitted bit is
only available.

0x08: Auto

Set the Target of block mode (MODE_BLK) to Auto or O/S according
to the Write Mode of the parameter to be set or changed.

22

MODE_BLK
(DS-37)

0x08: Auto

The mode parameter is a structured parameter composed of the
actual mode, the normal mode and the permitted mode.

Actual: Indicates the current operating condition.

Permit: Indicates the operating condition that the block is

allowed to take.

Normal: Indicates the operating condition that the block will

usually take.

Actual

O/S bit, Auto bit

The permitted bit is
only available.

0x80: O/S,
0x08: Auto

Permitted

0x08: Auto

Normal

23

ALARM_SUM
(DS-42)

0

Bit7 is only available.

The current alert status, unacknowledged status, unreported status
and disabled status of the alarms associated with the function block.

Current

24

CALIBR_FACTOR

O/S

O/S

1.0000

0.01 to 3.0000

Gain compensation value for the detector, so that flow indication is
accurate.
This parameter means the meter factor of low frequency side
(LOW_MF).
This parameter must not be downloaded by the operator.

25

26

LOW_FLOW_CUTOFF

0

The value which
corresponds to 0 to
10% of PV_SPAN
is permitted.

Set the low cut range corresponding 0 to 10 % of the large absolute
value between PV_SCALE.Array1 and PV_SCALE.Array2.
This value must be set to the lower switching point because this
function has a hysterisis.

O/S

MEASUREMENT_MODE

0: Unidirectional

0: Unidirectional
1: Bidirectional

Set the mode of the flow measurement,either unidirectional or
bidirectional.

27

O/S

FLOW_DIRECTION

0: Positive

0: Positive
1: Negative

Assign an arbitrary positive or negative sign to the measured PV
value.

28

O/S

ZERO_POINT

0.000

-999.9 to 999.9

This function shows the current zero point compensation value for
the sensor.
This parameter is used to display the results obtained from
ZERO_POINT_ADJUST . Specifically, the correction values
displayed, and it is also possible to directly enter correction values.
This parameter must not be downloaded by the operator.

29

Auto

ZERO_POINT_ADJUST

0: Cancel

0: Cancel
1: Execute

This parameter executes the automatic zero adjustment function: If
“Execute” is selected, this function will be started.
“Now Auto Zero Executing...” is indicated while the Auto Zero
function is being carried out and After finishing the adjustment, this
parameter is set to “Cancel”. The result of the automatic zero
adjustment is confirmed using ZERO_POINT , and if the result
exceeds the rated value, the warning “82: Auto Zero Wng” will be
displayed.

30

O/S

ZERO_POINT_UNIT

1062: mm/s

1062: mm/s

This parameter is used in order to select the unit for zero point.

31

O/S

NOMINAL_SIZE

Specified at
the time of
order

0.99 to 3000.10 (mm)
0.01 to 120.10 (inch)

This parameter is used in order to set the size (diameter) of the
sensor (flow tube).
If the setting value exceeds the valid range, the warning “72:Size Set
Err” will be displayed.

0

for future use

Unacknow-
ledged

0

for future use

Unreported

0

for future use

Disabled