4 easy setup, Easy setup -6 – Yokogawa AXFA14G/C User Manual
Page 30

IM 01E20F12-01E
5-6
5. EXPLANATION OF BASIC ITEMS
5.4 Easy Setup
Easy Setup tracks parameters that often need to be
configured or changed.
Click [Easy Setup] at the Navigation tree. It shows the
Easy setup window at the Parameter Set Application as
shown in Figure 5.2.5. The following figure is [Easy
Setup] window in the toggle the tree window mode,
and its contents is described Table 5.4.1.
Figure 5.4.1
Easy Setup
Table 5.4.1 Easy Setup Items
T0503.eps
Block name
Item
Type of Entry
TAG
Descriptor
Message
ASCII code
ASCII code
ASCII code
Transducer
Block
Target Mode
Actual Mode
Measured Value Unit
Alternative
Alternative
Monitor only
Filter Time
Numeric
Analog Input
Target Mode
Alternative
Monitor only
Numeric
Numeric
Numeric
Numeric
Actual Mode
Filter Time Const
PV Scale: Lower Value
PV Scale: Upper Value
Out Scale: Upper Value
Velocity Check
Numeric
Out Scale: Lower Value
Select 1
Alternative
Out Scale: Unit
Local Display
Select 2
Numeric
Out Scale: Decimal Point
Select 3
Monitor only
Alternative
Alternative
Alternative
The [Target Mode] in each function block must be set
from [AUTO] to [O/S] before changing parameters.
When the parameter in each item has been changed,
the DTM Works confirms its update, hence, press the
[Enter] key to fix. If the [ESC] key is pressed before
fixing, the data comes back to the set data without
changing.
Figure 5.4.2
Parameter change
The [Target Mode] must be returned [AUTO] when the
parameter setting work was finished.
IMPORTANT
Do not turn power OFF immediately after param-
eter setting. When parameters are saved to the
EEPROM, the redundant processing is executed
for an improvement of reliability. Should the
power be tumed OFF within 60 seconds after
setting of parameters, changed parameters are
not saved and may return to their original values.