5. EXPLANATION OF BASIC ITEMS
5.5 Function Blocks Setting
This section describes the procedure taken to set and
change the parameters for each block. Obtaining access
to each parameter differs depending on the configura-
tion system used. For detail, refer to Chapter 4 for each
configuration system.
Block mode consists of the following four modes that
are controlled by the universal parameter that displays
the running condition of each block.
- TARGET_MODE: Sets the operating condition of the
block.
- Actual: Indicates the current operating condition.
- Permit: Indicates the operating condition that the
block is allowed to take.
- Normal: Indicates the operating condition that the
block will usually take.
Table 5.5.1 shows the operating conditions which the
individual blocks will take.
Table 5.5.1 Operating condition in each function block
T0504.eps
Automatic
(Auto)
AI
block
Yes
TOT
block
Yes
DI
block
Yes
Transducer
block
Yes
Physical
block
Yes
Manual
(Man)
Yes
Yes
Yes
Out of
Service
(O/S)
Yes
Yes
Yes
Yes
Yes
The [Target Mode] in each function block must be set
from [AUTO] to [O/S] before changing parameters,
and then, return [AUTO] this mode after finish the
parameter setting work.
5.5.1 Physical Block Parameters Setup
There are 5 kinds of submenus as [Identification],
[Diagnosis], [Simulate Diagnosis], [Function Block
Status] and [Configuration].
Refer to section 6.3.4 for [Simulate Diagnosis] func-
tion.
Figure 5.5.1
Physical Block menu
(1) Configuration setting
There are 2 items to set parameters as [Write Locking]
and [Factory Reset] at [Configuration] in the [Physical
Block] menu. The write locking function enables to use
not only parameter setting but also setting by hardware
switch at the same time. Refer to section 3.5 detail.
Figure 5.5.2
Configuration Setup