Watlow Silver Series Addendum User Manual
Page 41
Silver Series OIT
41
Watlow Addendum
11) Click OK to close the Address dialog
12) For Mode choose External Trigger.
13) For Trigger address PLC name choose the OIT (Local HMI by default).
14) For Trigger address Device type choose LB to use an internal bit to cause the OIT to store
values in a recipe.
15) In Trigger address Address type 500.
16) Click the Label tab.
17) Check Use label.
18) Set State to 0.
19) In Content type the name of the parameter.
20) Click OK.
21) Place the Data Transfer (Trigger-based) object on the screen.
Repeat the following steps to create the data transfer items that will load recipes in to the
controller:
Note: For the data transfer objects that load the recipe from the OIT to the controller, the source
addresses are RW (recipe words) addresses in the OIT and the destination addresses are the parameters’
Modbus addresses in the controller.
Parameter
“Source”
Recipe
Address
Size in
Words
“Destination” Address in Controller
RMC
RMH
PM
ST
ST GTW*
Closed Loop Set Point
0
2
2501
5221
2161
22
2161
Alarm High Set Point
2
2
1741
2661
1481
98
1481
Heat Proportional Band
4
2
2231
4111
1891
233
1897
Integral
6
2
2235
4115
1895
227
1891
Derivative
8
2
2237
4117
1897
229
1893
*ST via RUI Gateway