Silver Series OIT

 32 

Watlow Addendum

To copy data to the OIT’s local memory:

1) From the Objects

menu choose Data
Transfer (Time-
based)
.

2) For each item to be

logged in the file:

• Click New…

(041)

• In Description type a

description of the data
to be copied such as
“PV 1”.

• For Address type

choose Word.

• For Interval choose a

value that is the same as
or less than the amount
of time you want
between data samples.

• In No. of words type

word size of the
parameter’s data type.
See table.

• For Source address

PLC name choose
Modbus RTU Master or
Modbus TCP/IP
Master
.

• For Source address

device type choose 4x.

• In Source address

Address type the
address of the parameter
to be logged.

(042)

Data Type

No. of words

Float

2

16-bit integer

1

32-bit integer

2

For this controller…

This
parameter…

Enter this
Address*…

Choose this
Data Type…

RMCxxxx-xxxxxxx

Analog Input 1
Process Value

361

32-bit Float

RMHx-xxxx-x1xxx

381

32-bit Float

PMxxxxx-xxxxxxx

361

32-bit Float

STxx-xxMx-xxxx

20

32-bit Float

ST via RUI Gateway

361

32-bit Float

Other Controllers

Consult the controller manual.

*These addresses have already been changed to the absolute form required
for EasyBuilder5000 by adding 1 to the value listed in the Watlow manual.
Enter them as listed.

• For Destination address PLC name choose the OIT (“Local HMI” by default).
• For Destination address device type choose LW.
• In Destination address Address type the local address at which to save the data to be logged.