Silver Series OIT

 18 

Watlow Addendum

5) For Address choose 4x

and enter the address
of the Closed Loop
Working/Active Set
Point for your
controller. See the
table.

6) Click the Numeric

Format tab.

7) In Data format set the

data type. See the
table.

8) On the Font tab set

Align to Right.

(013)

For this
controller…

This
parameter…

Enter this
Address*…

Choose this
Data Type…

RMCxxxx-xxxxxxx

Closed Loop
Working/Active
Set Point
(Read Only)

2513

32-bit Float

RMHx-xxxx-x1xx

5233

32-bit Float

PMxxxxx-xxxxxxx

2173

32-bit Float

STxx-xxMx-xxxx

204

32-bit Float

ST via RUI Gateway

2173

32-bit Float

Other Controllers

Consult the controller manual.

*These addresses have already been changed to the absolute form required
for EasyBuilder5000 by adding 1 to the value listed in the Watlow manual.
Enter them as listed.

9) Click OK.

10) Move the cursor with

the outline to position
the display field and
click to place it.

11) Adjust the size of the

field as needed.

12) From the File menu

choose Save.

(014)