Environmental characteristics – Proface LT4300M - 5.7 Modular HMI + Control" User Manual
Page 30

LT System General Implementation Rules
30
Environmental Characteristics
Enclosure Requirements
LT system components are designed as Zone B, Class A industrial equipment according to
IEC/CISPR Publication 11. If they are used in environments other than those described in the
standard, or in environments that do not meet the specifications in this manual, the ability to meet
electromagnetic compatibility requirements in the presence of conducted and/or radiated
interference may be reduced.
All LT system components meet European Community (CE) requirements for open equipment as
defined by EN61131-2. You must install them in an enclosure designed for the specific
environmental conditions and to minimize the possibility of unintended contact with hazardous
voltages. Use a metal enclosure to improve the electromagnetic immunity of your LT system. Use
enclosures with a keyed locking mechanism to minimize accidents
Environmental Characteristics
LT meets CE requirements as indicated in the table below, and is intended for use in a Pollution
Degree 2 industrial environment.
The table below gives the general environmental characteristics:
Characteristic
Specification
Standard
compliance
IEC61131-2
Ambient operating
temperature for the
display and the
rear module
Horizontal installation
0...50
° C (32...122° F)
Vertical installation
0...40
° C (32...104° F)
Storage temperature
- 20...60
° C (- 4...140° F)
Storage altitude
0...10,000 m (0...32,808 ft)
Operating altitude
0...2,000 m (0...6,560 ft)
Surrounding Air and Storage Humidity
5...85% w/o condensation (non-condensing, wet
bulb temperature 39
° C (102.2° F) or less)
Degree of pollution IEC60664
2
Degree of
protection
IEC61131-2
IP20 with protective covers in place
Corrosive gases
Free of corrosive gases
Dust
≤ 0.1 mg/m
3
(10
-7
oz/ft
3
) (non-conductive levels)
Atmospheric pressure (Operating Altitude)
800...1,114 hPa (2000 m (6,561 ft) or lower)
Vibration
resistance
Mounted on a DIN rail
3.5 mm (0.138 in.) fixed amplitude from 5...8.4 Hz
9.8 m/s
2
(1 g
n
) fixed acceleration from 8.4...150 Hz
Mounted on a panel
3.5 mm (0.138 in.) fixed amplitude from 5...8.6 Hz
9.8 m/s
2
(1 g
n
) fixed acceleration from 8.6...150 Hz
Mechanical shock
resistance
Mounted on a DIN rail
147 m/s
2
(15 g
n
) for a duration of 11 ms
Mounted on a panel
147 m/s
2
(15 g
n
) for a duration of 6 ms