LT-4201TM/4301TM Hardware Manual
109
1
Multipoint grounding is permissible if connections are made to an equipotential ground plane
dimensioned to help avoid shielded cable damage in the event of power system short circuit
currents.
WARNING
UNINTENDED EQUIPMENT OPERATION
Use shielded cables wherever specified for inputs, outputs, and communication connections.
Properly ground the cable shields as indicated in the related documentation.
Route communication and I/O cables separately from power cables.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
NOTICE
INOPERABLE EQUIPMENT
Be sure that the physical wiring of the analog circuit is compatible with the software configuration
for the analog channel.
Failure to follow these instructions can result in equipment damage.