Warning – Proface LT4300M - 5.7 Modular HMI + Control" User Manual
Page 139
LT-4201TM/4301TM Hardware Manual
139
Analog Output Characteristics
The table describes the characteristics of the analog outputs:
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not exceed any of the rated values specified.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Characteristic
Voltage Output
Current Output
Maximum number of outputs
2
Output range
-10... 10 Vdc/0...10 Vdc
0...20 mA / 4...20 mA
Load impedance
2 k
Ω or more
300
Ω or less
Application load type
Resistive load
Settling time
10 ms
Total output system transfer time
10 ms + 1 scan time
Output tolerance
Maximum
deviation at
25
° C (77° F)
without
electromagnetic
disturbance
± 1% of the full scale
Maximum
deviation
± 2.5% of the full scale
Digital resolution
12 bits
Temperature drift
± 0.06% of the full scale
Output ripple
± 50 mV
Cross talk
60 db
Non-linearity
± 0.5% of the full scale
Output value of LSB
6 mV
12
μΑ
Protection type
Photo coupler between input and internal circuit
Output protection
Short circuit protection: Yes
Open circuit protection: Yes
Output behavior if input power supply
is less than the power failed threshold
Set to 0
Cable
Type
Shielded
Length
Must be less than 3 m for IEC61131-2
conformance. Maximum transmission distance is
10 m.
Terminal blocks
Type: 3.5 mm (0.137 in.) pitch
Terminal blocks are removable
Isolation
External input: Photo coupler isolation
Between channels: Non-isolated