Analog inputs and analog outputs – Proface LT4300M - 5.7 Modular HMI + Control" User Manual
Page 136

136
Analog Inputs and Analog Outputs
Analog Input Characteristics
The table describes the characteristics of the analog inputs:
Characteristic
Voltage input
Current input
Number of maximum input channels
2
Input type
Single-ended
Input range
-10... 10 Vdc/0...10 Vdc
0...20 mA/4...20 mA
Input impedance
1 M
Ω or more
250 ± 0.11%
Ω
Sample duration time
10 ms per channel + 1 scan time
Total input system transfer time
20 ms + 1 scan time
Input tolerance
Maximum deviation
at 25
° C (77° F)
without
electromagnetic
disturbance
± 1% of the full scale
Maximum deviation
± 2.5% of the full scale
Digital resolution
13 bits
Temperature drift
± 0.06% of the full scale
Common mode characteristics
80 db
Cross talk
60 db
Non-linearity
± 0.4% of full scale
Input value of LSB
5 mV
10
μΑ
Maximum allowed overload (no
damages)
± 30 Vdc (less than
5 minutes)
± 15 Vdc (No damage)
± 30 mA dc
Protection type
Photo coupler between input and internal circuit
Cable
Type
Shielded
Length
Must be less than 3 m for IEC61131-2
conformance. Maximum transmission distance is
10 m.
Terminal blocks
Type: 3.5 mm (0.137 in.) pitch
Terminal blocks are removable
Isolation
External input: Photo coupler isolation
Between channels: Non-isolated