Warning – Proface LT4300M - 5.7 Modular HMI + Control" User Manual
Page 122
![background image](/manuals/358956/122/background.png)
Communication Interface
122
The table describes the pins of the CANopen interface:
The shield is connected to pin 6, the 0 Vdc pin.
NOTE: Pin 9 is not connected internally. The controller does not provide power on CAN_V+.
Status LED
The table describes the CAN status LED:
The table describes the CAN STS status LED:
NOTE: CanOpen LED is mounted alongside the cover.
PIN
Signal
Description
1
N.C.
Reserved
2
CAN_L
CAN_L bus Line (Low)
3
CAN_GND
CAN 0 Vdc
4
N.C.
Reserved
5
CAN_SHLD
N.C.
6
GND
0 Vdc
7
CAN_H
CAN_H bus Line (High)
8
N.C.
Reserved
9
N.C.
Reserved
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not connect wires to unused terminals or terminals marked “Not Connected (N.C.)”.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Marking
Description
LED
Color
Description
CAN STS
CANopen status
Green / Red
See CAN STS status LED below
CAN0 LED
CANopen Status
Description
OFF
No CANopen
configured
CANopen is not active in the application.
Single flash red /
with green ON
Acceptable detected
error limit threshold
has been reached
The controller has detected that the maximum
number of error frames has been reached or
exceeded.
Double flash red /
with green ON
Node Guarding or
Heartbeat event
The controller has detected either a Node
Guarding or Heartbeat exception for the
CANopen master or slave device.
Red ON
Bus off
The CANopen bus is stopped.
Green ON
The CANopen bus is operational.